Appendix C Reference; Appendix C.1. Est3 Data Format; Appendix C.1.1. Input Data Format - FieldServer FS-8700-39 Driver Manual

Est3-ecp driver
Table of Contents

Advertisement

FS-8700-39 EST3 Driver Manual
Appendix C. Reference
EST3 Data Format:

Appendix C.1.1. Input data format

Each input device is associated with a 16-bit value. The contents of the 16 bits are used to generate status types as shown in
the table below. Each incoming event is allocated to a status type depending on its device type as shown in the table. It is
possible to override this default status type allocation. Refer to 0 for more information.
Type
Smoke
Pull
Heat
Waterflow
Stagetwo
Zone
AlarmVerify
PreAlarm
Security
Station
Emergency
Supervisory
Valve
GateValve
Tamper
Temperature
Power
Signal
TroubleOpen
TroubleShort
LocalTrouble
MaintAlert
DirtyHead
DeviceComm
GroundFault
InternalTrouble
BadType
BadPersonality
UnexpectedDevice
CommonTrouble
RelayConfirmation
Monitor
LocalMonitor
Damper
Fan
Door
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Encode Value
Alarm
Trouble
0
Y
1
Y
2
Y
3
Y
4
Y
5
Y
6
Y
7
Y
8
Y
9
10
Y
11
12
13
14
15
16
17
18
Y
19
Y
20
Y
21
Y
22
Y
23
Y
24
Y
25
Y
26
Y
27
Y
28
Y
29
Y
30
31
32
33
34
35
Supervisory
Monitor
CO Active
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y