FieldServer FS-8700-130 Driver Manual page 21

Fieldserver technologies server computer drive driver manual
Table of Contents

Advertisement

FS-8700-130 Notifier NCA2/NFS-3030 Manual
Error
#2 Err. Reset/Normal
queue<%d>
full
on
MD<%s>
#3 FYI. Event<%s> not
Supported.
#4 Err. Unknown Node
Trouble <%s>
#5 Err. Unknown OFF
NETWORK Node <%s>
#6 Err. Unsupported
Point
Address
Format<%s>
#7 FYI. Attempt to
decrement below zero
offset<%d> DA<%s>
2
All Data Arrays on the FieldServer are initialized to zero on rebooting or starting up. A zero value in the Data Array assumes no problems with
the devices, but if a problem existed before the startup and the device comes out of problem, the FieldServer will attempt to decrease the
number of problems by 1 and this generates the error. Data from the FieldServer should not be considered reliable until the "System Normal"
message has been returned.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com
Description
This driver keeps track of all non-zero
memory locations per Map Descriptor.
When the track queue is full, the oldest
offset is overwritten with the latest
one.
This could be a problem on
System_Reset
and
System_Normal
where memory locations get cleared as
per this queue.
The
FieldServer
received
unrecognized
event
or
message.
The FieldServer received a Node
Trouble
event
not
listed
Appendix A.2 or a corrupted message.
The FieldServer received a message
that a Node either connected or
disconnected from the network, but no
Node number was received - it is likely
that the message was corrupted
A message was received from an
unsupported device or the address of
the device is not in the correct
format/location.
The driver attempted to decrement the
trouble counting number to a number
less than 0.
Action
If the error occurs during installation or
testing, it can be ignored.
occurs during field operation, configure the
Map Descriptor with required address
ranges only and keep the Map Descriptor
length smaller than the queue length.
an
If the error occurs continuously, check that
corrupted
connection parameters match with panel
port settings.
If this error occurs continuously and you
under
need this new trouble status, contact
FieldServer.
Call Tech support.
Call Tech support.
This occurs due to poor synchronization
between the FieldServer and the Notifier
panel or because a problem existed before
2
connection.
. It will rectify itself upon
"System Normal" message. Check the
configuration file to identify the address
and memory area type mapped to this
offset and the Data Array which is causing
the error.
Page 21 of 21