FieldServer FS-8700-130 Notifier NCA2-NFS2-3030 Instruction Manual

Nca2/nfs2-3030 serial driver
Hide thumbs Also See for FS-8700-130 Notifier NCA2-NFS2-3030:

Advertisement

Quick Links

-
(Supplement to the FieldServer Instruction Manual)
FS-8700-130 Notifier NCA2-NFS2-3030
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after January 2009
Driver Manual
Driver Version:
1.02
Document Revision:
1

Advertisement

Table of Contents
loading

Summary of Contents for FieldServer FS-8700-130 Notifier NCA2-NFS2-3030

  • Page 1 Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-130 Notifier NCA2-NFS2-3030 APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after January 2009 Driver Version: 1.02 Document Revision:...
  • Page 2: Table Of Contents

    Appendix B.1. Connection Tips & Hints ........................20 Appendix B.2. Networking Tips ..........................20 Appendix C. Error Messages ..........................21 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 3: Notifier Nca2/Nfs2-3030 Description

    If a networked panel does not send the 'CLEARED' message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done. It is possible to configure the FieldServer to clear on reset message from NCA2.
  • Page 4: Hardware Connections

    FS-8700-130 Notifier NCA2/NFS-3030 Manual Page 4 of 22 HARDWARE CONNECTIONS The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection drawing. Configure the Notifier Panel according to manufacturer’s instructions. RJ45 Notifier NCA2/NFS2-3030 Rx (Brown)
  • Page 5: Hardware Connection Tips / Hints

    Page 5 of 22 Hardware Connection Tips / Hints • The FieldServer should preferably be connected to the TB5 Printer port. It is theoretically possible to connect to the TB5 CRT port, but this has not been fully tested. •...
  • Page 6: Configuring The Fieldserver As A Notifier Nca2/Nfs2-3030 Client

    Page 6 of 22 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2/NFS2-3030 CLIENT For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv”...
  • Page 7 Memory Type : Panel_Trouble Troubles/Faults 1–96 Memory Type : Bell_Trouble Troubles/Faults Table 1 – Memory Mapping Address Structure. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 8: Data Arrays/Descriptors

    Page 8 of 22 Data Arrays/Descriptors The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Notifier NCA2/NFS2-3030 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes”...
  • Page 9: Client Side Connection Descriptions

    Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 10: Client Side Map Descriptors

    Specify whether driver should clear Node(s) Clear_on_Normal* memory area upon receipt of “SYSTEM NORMAL” Yes ,No message from Panel. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 11: Map Descriptor Example: Standard Example

    Map Descriptor Type starting address for data storage from the Notifier panel. will store data and length FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 12: Configuring The Fieldserver As A Notifier Nca2/Nfs2-3030 Server

    Page 12 of 22 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2/NFS2-3030 SERVER This driver cannot be configured as a Server. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 13: Appendix A. Advanced Topics

    “Cleared” SYSTEM RESET message configured Clear_on_Reset. default Clear_on_Reset is ‘no’. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 14: Appendix A.2. System Trouble Messages

    STYLE \4\" WIRING OR LOOP #10 ABNORMAL" ANNUN 4 TROUBLE UNPROGRAMMED DEVICE ON LOOP 1 ANNUN 5 TROUBLE UNPROGRAMMED DEVICE ON LOOP 2 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 15 REMOTE DISPLAY 31 TROUBLE MAPPING IN PROGRESS LOOP 10 REMOTE DISPLAY 32 TROUBLE LIB #1 SCB RECEIVE ERROR FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 16 DATABASE CORRUPTED REMOTE DISPLAY 6 NO ANSWER AUDIO LIBRARY CORRUPTED REMOTE DISPLAY 7 NO ANSWER LCD80 SUPERVISORY FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 17 LOOP CONTINUITY TEST FAIL LOOP 1 DIB CODE MEMORY CHECKSUM ERROR LOOP CONTINUITY TEST FAIL LOOP 2 INCOMPATIBLE SOFTWARE OR INVALID CBE FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 18: Appendix A.3. Node Status

    Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the NCA2 Panel is lost.
  • Page 19: Appendix A.5. Driver Limitations And Exclusions

    • Zone information will not be recorded. • To synchronize the FieldServer with the panel, connect the running FieldServer and press the “System Reset” button on the panel. All current events will be re-sent to the FieldServer. • The port must be enabled on the unit and set to 80 columns with NO supervision •...
  • Page 20: Appendix B. Troubleshooting Tips

    Communication errors will be experienced if the port is disabled at the panel. Please check the Notifier Manuals on how to enable the panel port connected to the FieldServer and ensure that it is set to 80 columns NO supervision.
  • Page 21: Appendix C. Error Messages

    Call Tech support. NETWORK Node <%s> Node number was received - it is likely that the message was corrupted FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com...
  • Page 22 All Data Arrays on the FieldServer are initialized to zero on rebooting or starting up. A zero value in the Data Array assumes no problems with the devices, but if a problem existed before the startup and the device comes out of problem, the FieldServer will attempt to decrease the number of problems by 1 and this generates the error.