Check Equipment Location
Recommendations for your equipment location.
Note
Extreme Networks recommends that you consult an electrical contractor for commercial
building and wiring specifications.
1
Be sure that your system is readily accessible for installation and service.
See
Rack Specifications and Recommendations
2 Use appropriate AC or DC power, power distribution, and grounding for your specific installation.
3 Use a vinyl floor covering in wiring closets or other indoor equipment locations.
Concrete floors accumulate dust, and carpets can cause static electricity.
4 Prevent unauthorized access to equipment locations by providing door locks.
Install the equipment in a secured, enclosed, and restricted access location, ensuring that only
qualified service personnel have access to the equipment.
5 Provide adequate overhead lighting for easy maintenance.
6 Be sure that each equipment location has a suitable ground.
All equipment racks and equipment installed in the closet should be grounded.
7 Be sure that all system environmental requirements are met, such as ambient temperature and
humidity.
Control Temperature
It is important to keep installed equipment within the thermal operating specifications for optimum
performance and safety.
Install the equipment only in a temperature- and humidity-controlled indoor area that is free of
airborne materials. Too much humidity can cause a fire. Too little humidity can produce electrical shock
and fire.
Note
As with all electrical equipment, Extreme Networks product lifetimes degrade with increased
temperature. If possible, temperatures should be kept at approximately 78° F (25° C) or
lower.
1
Be sure that the ventilation in the wiring closet is adequate to maintain a temperature below 104° F
(40° C).
2 Install a reliable air conditioning and ventilation system.
3 Keep the ventilation in the wiring closet running during non-business hours; otherwise, the
equipment can overheat.
4 Maintain an ambient operating temperature of 32° to 104° F (0° to 40° C).
5 Maintain a storage temperature of -40° to 158° F (-40° to 70° C).
Control Humidity
Maximize equipment life by keeping relative humidity between allowable limits.
BlackDiamond X8 Series Switches Hardware Installation Manual
for information.