Extreme Networks BlackDiamond X8 Series Hardware Installation Manual

Hide thumbs Also See for BlackDiamond X8 Series:
Table of Contents

Advertisement

BlackDiamond X8 Series
Switches Hardware Installation
Manual

Advertisement

Table of Contents
loading

Summary of Contents for Extreme Networks BlackDiamond X8 Series

  • Page 1 BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 2: Trademarks

    ExtremeWorks, ExtremeXOS, Go Purple Extreme Solution, ExtremeXOS ScreenPlay, ReachNXT, Ridgeline, Sentriant, ServiceWatch, Summit, SummitStack, Triumph, Unified Access Architecture, Unified Access RF Manager, UniStack, XNV, the Extreme Networks logo, the Alpine logo, the BlackDiamond logo, the Extreme Turbodrive logo, the Summit logos, and the Powered by ExtremeXOS logo are trademarks or registered trademarks of Extreme Networks, Inc.
  • Page 3: Table Of Contents

    Table of Contents Trademarks 0 Preface 5 Audience 5 Conventions 5 Related Publications 6 Chapter 1: BlackDiamond X8 Series Switches 7 Switch Overview 7 BlackDiamond X8 Chassis Features 7 Management Ports 9 Chapter 2: BlackDiamond X8 Series Modules and Fans 11 Module Overview 11 Management Module 12 I/O Modules 15...
  • Page 4 Table of Contents Chapter 8: Safety Information 91 Considerations Before Installing 91 Maintenance Safety 92 General Safety Precautions 92 Cable Routing for LAN Systems 93 Installing Power Supply Units and Connecting Power 93 Selecting Power Supply Cords 95 Battery Replacement and Disposal 95 Fiber Optic Ports and Optical Safety 95 Sicherheitshinweise 96 Überlegungen vor der Installation 97...
  • Page 5: Preface

    See the ExtremeXOS Concepts Guide and the ExtremeXOS Command Reference Guide for information about configuring the BlackDiamond X8 series switch. Note If the information in an installation note or release note shipped with your Extreme Networks equipment differs from the information in this guide, follow the installation or release note. Conventions The following list conventions used throughout this guide.
  • Page 6: Related Publications

    Extreme Networks Pluggable Interface Modules Installation Guide • ExtremeXOS Hardware and Software Compatibility Matrix Hardware and software documentation for Extreme Networks products is available from the Extreme Networks website. You can download software concepts guides and reference guides, hardware installation guides, and other documents at: www.extremenetworks.com/go/documentation.
  • Page 7: Chapter 1: Blackdiamond X8 Series Switches

    BlackDiamond X8 Series Switches Switch Overview BlackDiamond X8 Chassis Features Management Ports Switch Overview The BlackDiamond X8 series switches are chassis-based switches designed for virtualized data centers and high-performance compute cluster installations. They provide high-density, line rate 10/40 GbE ports. For more information about configuring a BlackDiamond switch, see the ExtremeXOS Concepts Guide and the ExtremeXOS Command Reference Guide.
  • Page 8 BlackDiamond X8 Series Switches Front of the BlackDiamond X8 Chassis shows a BlackDiamond X8 chassis equipped with management modules and I/O modules. Figure 1: Front of the BlackDiamond X8 Chassis 1 = Power supply cover 3 = Management modules 2 = ESD jack 4 = I/O modules The front of the chassis provides access to: •...
  • Page 9: Management Ports

    BlackDiamond X8 Series Switches Figure 2: Back of the BlackDiamond X8 Chassis 1 = Grounding point 3 = AC power input connectors 2 = ESD jack 4 = Fan trays The back of the chassis provides access to: • Eight AC power input connectors •...
  • Page 10 BlackDiamond X8 Series Switches This port allows you to communicate directly with the central processing unit (CPU) of the switch. You can plug an Ethernet cable directly from your laptop into the management port for direct access into the switch. This access allows you to view and locally manage the switch configurations. USB ports on the management module allow you to attach a single USB 2.0 flash drive.
  • Page 11: Chapter 2: Blackdiamond X8 Series Modules And Fans

    BlackDiamond X8 Series Modules and Fans Module Overview Management Module I/O Modules Fabric Modules Fan Trays Module Overview Modules for the switch include management modules, I/O modules, and switch fabric modules. Each module for the switch consists of a printed circuit board mounted on a metal panel. The module carrier also includes ejector/injector levers and captive retaining screws on the module front panel.
  • Page 12: Management Module

    BlackDiamond X8 Series Modules and Fans Table 3: Modules Available for the BlackDiamond X8 Series Switch (continued) Module Type Short Description Long Description Manufacturing No. (SKU) I/O module BDXA-10G48X 48-Port 10GBASE-X SFP+ 900851-10 module for BlackDiamond X series chassis. Up to eight modules in the BDX8 chassis support up to 384 wirespeed 10GbE ports...
  • Page 13: Redundant Management Module Activity

    BlackDiamond X8 Series Modules and Fans Redundant Management Module Activity The switch can operate with a single management module installed or with two management modules installed for redundancy. When you install a second management module, one of the management modules operates as the primary, and the other becomes the secondary or backup.
  • Page 14: Management Module Leds

    BlackDiamond X8 Series Modules and Fans • General fan status (FAN) • Fabric module status (FM) Figure 3: BDX-MM1 Module 1 = LEDs 3 = Console port 2 = Management port and USB ports 4 = Auxiliary port with LED Management Module LEDs LEDs on the management module provide status information about operation of the switch and major chassis components.
  • Page 15: I/O Modules

    BlackDiamond X8 Series Modules and Fans Table 4: LEDs on the BDX-MM1 Management Module (continued) Label/Function Color/State Meaning Amber/steady The fabric module is running diagnostics or has a fault condition. Fabric module status Check the FM LEDs on the fan trays at the rear of the chassis. (See LEDs for the BlackDiamond X8 Series Fabric Modules.) All the fabric modules are operating normally.
  • Page 16 BlackDiamond X8 Series Modules and Fans Figure 4: BDXA-10G48X I/O Module 1 = 10-gigabit Ethernet ports 2 = LEDs In the default configuration for the BDXA-10G48X module, all ports: • Are added to the default VLAN as untagged. • Inherit the properties of the default VLAN (for example, protocol type and VLAN ID). The BDXA-10G48X module has the following LEDs: •...
  • Page 17 BlackDiamond X8 Series Modules and Fans Figure 5: BDXA-40G24X I/O Module 1 = QSFP+ ports 2 = LEDs In the default configuration for the BDXA-40G24X module, all ports: • Are added to the default VLAN as untagged. • Inherit the properties of the default VLAN (for example, protocol type and VLAN ID). The BDXA-40G24X module has the following LEDs: •...
  • Page 18 BlackDiamond X8 Series Modules and Fans Figure 6: BDXA-40G12X I/O Module 1 = QSFP+ ports 2 = LEDs In the default configuration for the BDXA-40G12X module, all ports: • Are added to the default VLAN as untagged. • Inherit the properties of the default VLAN (for example, protocol type and VLAN ID). The BDXA-40G12X module has the following LEDs: •...
  • Page 19: Fabric Modules

    BlackDiamond X8 Series Modules and Fans • Port status For information about the LEDs and their activity on the BDXA-10G48T modules, see I/O Module LEDs. I/O Module LEDs LEDs on the front panel of the BlackDiamond X8 series I/O modules provide information about the operating status of the module and ports.
  • Page 20: Fan Trays

    BlackDiamond X8 Series Modules and Fans BDXA-FM10T fabric modules provide a total switch fabric capacity of 10 Terabits per second, and BDXA-FM20T fabric modules provide 20 Terabits per second. A switch fabric composed of BDXA-FM10T modules will provide full line rate for the BDXA-10G48X, BDXA-10G48T, and BDXA-40G12X I/O modules.
  • Page 21 BlackDiamond X8 Series Modules and Fans Figure 9: Fan Trays in the BlackDiamond X8 Chassis Table 7: LEDs for the Fan Trays Label/Function Color/State Meaning Stat Green Fans are operating normally. Amber/blinking One or more fans are not operating properly. No power.
  • Page 22: Chapter 3: Overview Of Power Supplies

    Field operators must not attempt to open the power supply enclosure for any reason; the power supply does not contain user-serviceable parts. In the event of failure, return the defective power supply to Extreme Networks for repair or replacement. The power supply bay in the switch can accommodate up to eight AC power supplies.
  • Page 23: Power Supply Cords

    An AC power cord is not included with the BlackDiamond X8 AC power supply. You can purchase AC power cords for use in the US and Canada from Extreme Networks or from your local supplier. An AC power cord for use with the BlackDiamond X8 AC power supply must meet the...
  • Page 24: Chapter 4: Site Preparation

    • Equipment rack requirements. 2 Evaluate and meet cable requirements. Evaluate and compare your existing cable plant with the requirements of the Extreme Networks equipment to determine if you need to install new cables. 3 Meet power requirements. To run your equipment safely, you must meet the specific power requirements for each router and external power supply unit installed in the system.
  • Page 25 Site Preparation Meet Operating Environment Requirements Learn the regulations for building codes and standards. Virtually all areas of the United States are regulated by building codes and standards. During the early planning stages of installing or modifying your network, it is important that you develop a thorough understanding of the regulations that pertain to your location and industry.
  • Page 26 Too much humidity can cause a fire. Too little humidity can produce electrical shock and fire. Note As with all electrical equipment, Extreme Networks product lifetimes degrade with increased temperature. If possible, temperatures should be kept at approximately 78° F (25° C) or lower.
  • Page 27: Rack Specifications And Recommendations

    Follow Spacing Requirements and Airflow Be sure that walls and other equipment do not block the air intake or outflow on an Extreme Networks switch. Leave a minimum of 24 inches (61 cm) between any cabinet wall or other obstruction and the front and back of the chassis.
  • Page 28 Use a rack grounding kit and a ground conductor that is carried back to earth or to another suitable building ground. All Extreme Networks switches are designed with mounting brackets that provide solid metal-to-metal connection to the rack. If you do not use equipment racks, you can attach wiring terminals directly to the mounting brackets for appropriate grounding.
  • Page 29: Evaluate And Meet Cable Requirements

    Cabling Standards Use professional consultants for site planning and cabling Extreme Networks recommends using the Building Industry Consulting Service International (BICSI) Registered Communications Distribution Designer (RCDD), which is globally recognized as a standard in site planning and cabling. For information, go to www.bicsi.org.
  • Page 30: Cable Distances

    2 Assign a unique block of sequential numbers to the group of cables that run between each pair of equipment locations. 3 Assign a unique identification number to each equipment rack. 4 Identify all equipment locations by labeling the front panel of your Extreme Networks equipment and other hardware. 5 Keep accurate and current cable identification records.
  • Page 31 50 mm multimode fiber (OM4) 150 meters * Proprietary to Extreme Networks. Connections between two Extreme Networks 1000BASE-LX interfaces that use 10/125 µm single-mode fiber can use a maximum distance of 10,000 meters. Table 11: Copper Cable Category, Transmission Rate, and Maximum Cable Distances...
  • Page 32 Every cable has a minimum bend radius, example, and fibers will be damaged if the cables are bent too sharply. It is also important not to stretch the cable during installation. Extreme Networks recommends BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 33: Meet Power Requirements

    Site Preparation that the bend radius for fiber optic cable equal 2 inches (5.08 cm) minimum for each 90-degree turn as shown in Bend Radius for Fiber Optic Cable Bend Radius for Fiber Optic Cable. Note Kinks and sharp bends can destroy or impair the cable’s ability to convey light pulses accurately from one end of the cable to the other.
  • Page 34: Ac Power Cord Requirements

    AC Power Cord Requirements AC power input cords are not included with BlackDiamond X8 power supplies. You can purchase AC power cords for use in the US and Canada from Extreme Networks or from your local supplier. Make sure that the power cord you use is certified for the country of end use and suitable for the device.
  • Page 35: Uninterruptible Power Supply Requirements

    VA = Volts x Amperes 3 Add the VA from all the pieces of equipment together to find the total VA requirement. 4 Add 30% to the total (recommended by Extreme Networks)to determine the minimum volt- amperage requirements for your UPS.
  • Page 36: Applicable Industry Standards

    UPS Transition Time Transition time is the time that is necessary for the UPS to transfer from utility power to full-load battery power. For Extreme Networks products, a transition time of less than 20 milliseconds is required for optimum performance.
  • Page 37: Chapter 5: Installing A Blackdiamond X8 Series Chassis

    Save all packaging, bolts, and washers, as well as the box and pallet, for future use in the event that the chassis must be moved to another location or returned to Extreme Networks. Refer to the illustrations printed on the BlackDiamond X8 shipping container and unpack the chassis...
  • Page 38 Installing a BlackDiamond X8 Series Chassis Cut the straps around the box. Figure 14: Unstrapping the Box 2 Slide the box up and off the chassis and interior packing foam. Figure 15: Removing the Box 3 Remove the inside corner braces. 4 Remove the support brackets and boxed accessories and set them aside until you need them.
  • Page 39 Installing a BlackDiamond X8 Series Chassis 6 Pull apart the keyed corner of the lower packing foam and remove the lower packing foam from around the chassis. Figure 16: Removing the Accessories and Foam 7 On each side, remove the restraining bolts from the shipping brackets at the front and middle of the chassis.
  • Page 40 Installing a BlackDiamond X8 Series Chassis c Set the fan tray aside in a safe place. Figure 18: Removing the Fan Trays 9 Open the accessory box and locate the four lifting handles. 10 On each side of the chassis, set the pegs on the lifting handles into the mounting holes. Figure 19: Preparing to Lift the Chassis from the Pallet Caution Never use the handles on the fan assemblies to lift the chassis.
  • Page 41: Pre-Installation Requirements

    Installing a BlackDiamond X8 Series Chassis Pre-Installation Requirements In addition to the support brackets that are shipped with the chassis, you need the following tools and equipment to install a chassis: • Mid-mount bracket kit (model number 48020, ordered separately from the chassis) •...
  • Page 42 Installing a BlackDiamond X8 Series Chassis b Using a #2 Phillips screwdriver, insert and tighten the mounting screws to secure the bracket to the chassis. Figure 20: Attaching Mid-mount Brackets 2 Identify the rack location where the chassis will be installed. BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 43 Installing a BlackDiamond X8 Series Chassis 3 Using four rack mounting screws, attach the support bracket to the equipment rack immediately below the intended chassis location. Screws are not provided. To provide wider support for the chassis as you install it, you can attach the second support bracket on the other side of the rack post.
  • Page 44: Ground The Chassis

    Installing a BlackDiamond X8 Series Chassis 8 Check to ensure screws are secure. Figure 22: Securing the Chassis to the Rack 9 After the chassis is secured to the equipment rack, ground the chassis. Ground the Chassis Although grounding the chassis is optional, it is recommended to do so. You must provide the following materials to ground the chassis: •...
  • Page 45: Install Power Supplies

    Installing a BlackDiamond X8 Series Chassis Identify the grounding pad on the back of the chassis. Figure 23: Grounding Pad on the Chassis 1 = Grounding pad 2 Strip 0.5 inch (1.2 cm) of insulation from the stranded copper wire cable. 3 Insert the stripped wire into the cable lug.
  • Page 46 Installing a BlackDiamond X8 Series Chassis c Lift the cover panel away from the chassis. Figure 24: Removing the Power Supply Ventilation Cover 2 Identify the power supply bay where you will install the power supply. Power supply bays are numbered from 1A to 8B. To establish an N+N redundant power configuration, install power supplies in both the upper and lower rows.
  • Page 47 Installing a BlackDiamond X8 Series Chassis 4 Slide the power supply into the chassis until the lever starts to engage. Figure 26: Installing a Power Supply 5 Rotate the lever toward the front of the power supply to fully seat the power supply in the chassis. 6 Repeat steps to install other power supplies as required by your system configuration.
  • Page 48: Connect Power

    Installing a BlackDiamond X8 Series Chassis c Align and tighten the retaining screws. Caution Do not operate the switch without the power supply cover in place. This cover is required to maintain proper EMI levels for the switch. Figure 27: Installing the Power Supply Ventilation Cover Connect Power Use this procedure to connect the AC power cords and the cord retainer.
  • Page 49 Installing a BlackDiamond X8 Series Chassis 3 Align and tighten the captive retaining screws on the power cord retainer. Figure 29: Installing the AC Power Cord Retainer BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 50: Chapter 6: Installing Blackdiamond X8 Series Modules

    Installing BlackDiamond X8 Series Modules Installation Order Required Tools Install Fabric Modules Install Management Modules Install I/O Modules Initial Management Access Installation Order For an initial system installation, the recommended order for populating the chassis is: Install all fabric modules (FMs). 2 Install all management modules (MMs).
  • Page 51 Installing BlackDiamond X8 Series Modules 3 Remove the fan tray from each location where you will install a fabric module. Figure 30: Removing a Fan Tray 4 Install each fabric module. BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 52 Installing BlackDiamond X8 Series Modules a Loosen the screws on the insertion/extraction levers and open the levers. Figure 31: Installing a Fabric Module b Align the circuit board with the guides at the top and bottom of the chassis and slide the module into the chassis.
  • Page 53 Installing BlackDiamond X8 Series Modules c When the levers start to engage, push them toward the module to seat the module in the chassis. d Align and tighten the retaining screws to fasten the module in place. Figure 32: Securing a Fabric Module 5 Repeat these steps to install additional fabric modules.
  • Page 54: Install Management Modules

    Installing BlackDiamond X8 Series Modules b Align and tighten the retaining screws. Figure 33: Installing a Fan Tray Install Management Modules Slots for management modules are labeled A and B. Install the first management module in slot A. Attach the ESD-preventive wrist strap to your bare wrist. 2 If it is not already connected, connect the metal end to the receptacle between the management module slots.
  • Page 55 Installing BlackDiamond X8 Series Modules 7 Use the lever to fully seat the module internal connectors. Figure 34: Seating the Management Module 8 Use a # 2 Phillips screwdriver to lock the handle into place. When the locking screw is fully tightened, the yellow band around the screw head is completely hidden.
  • Page 56: Install I/O Modules

    The shipping cover maintains the mechanical stability of the chassis during shipping. 2 Keep the shipping cover and store it with the other chassis shipping materials, in case you need to move the chassis or return it to Extreme Networks. 3 Attach the ESD-preventive wrist strap to your bare wrist.
  • Page 57 Installing BlackDiamond X8 Series Modules 6 Verify that the module injector/ejector handles are open. Keep the injector/ejector handles in the open position as you slide the module into the chassis slot. Figure 36: Installing an I/O Module Note If the injector/ejector handles are in the latched position, they prevent the module from sliding all the way into the slot.
  • Page 58 Installing BlackDiamond X8 Series Modules 9 Use a # 2 Phillips screwdriver to lock each handle into place. When a locking screw is fully tightened, the yellow band around the screw head is completely hidden. Caution Be careful to avoid over-torquing and stripping the screw heads. Figure 37: Locking the Module into Place I/O Module Blanks Switches are shipped with a reinforcement shipping cover installed over all the I/O module slots.
  • Page 59: Initial Management Access

    Installing BlackDiamond X8 Series Modules 2 Align the module blank with the card guides for the open slot on the chassis. Figure 38: Installing a Module Blank 3 Use a #2 Phillips screwdriver to tighten the captive screws at each end of the module blank.Tighten the screws of each installed module blank before inserting additional modules or blanks.
  • Page 60 Parity: None • Flow control: XON/XOFF The terminal or PC with terminal-emulation software that you connect to an Extreme Networks switch must be configured with these settings. This procedure is described in the documentation supplied with the terminal. Appropriate cables are available from your local supplier, or you can make your own. To ensure the electromagnetic compatibility of the unit, use only shielded serial cables.
  • Page 61 Installing BlackDiamond X8 Series Modules 7 Type save. Your configuration changes are saved so that they will be in effect after the next system reboot. The configuration is saved to the configuration database of the management modules in the switch. 8 Type logout.
  • Page 62: Chapter 7: Blackdiamond X8 Maintenance Procedures

    BlackDiamond X8 Maintenance Procedures Replace a Power Supply Replace a Fan Tray Replace a Fabric Module Replace a Management Module Reseating a management module DIMM Pack the Chassis for Shipping Replace a Power Supply You need a #2 Phillips screwdriver to remove the power supply ventilation cover. Remove the power supply ventilation cover.
  • Page 63 BlackDiamond X8 Maintenance Procedures 2 Push the release button for the inserter/extractor lever on the front of the power supply. 3 Rotate the inserter/extractor lever to the right to unseat the power supply from the internal connectors. 4 Carefully slide the power supply out of the chassis and set it aside. Figure 40: Removing a Power Supply 5 On the front of the replacement power supply, push the release button for the insertion/ejector lever.
  • Page 64 BlackDiamond X8 Maintenance Procedures 6 Slide the power supply into the chassis until the lever starts to engage. Figure 41: Installing a Power Supply 7 Rotate the lever toward the front of the power supply to fully seat the power supply in the chassis. 8 Replace the power supply ventilation cover.
  • Page 65: Replace A Fan Tray

    BlackDiamond X8 Maintenance Procedures c Align and tighten the retaining screws. Figure 42: Installing the Power Supply Ventilation Cover Caution Do not operate the BlackDiamond X8 switch without the power supply ventilation cover in place. This cover is required to maintain proper EMI levels for the switch. Replace a Fan Tray You need a #2 Phillips screwdriver to replace a fan tray.
  • Page 66 BlackDiamond X8 Maintenance Procedures 2 Holding both handles, pull straight outward on the fan tray to disconnect the internal connector. Figure 43: Removing a Fan Tray 3 Set the fan tray aside in a safe place. 4 Holding the replacement fan tray with both handles, align it with the opening and slide it straight into the chassis.
  • Page 67: Replace A Fabric Module

    BlackDiamond X8 Maintenance Procedures 5 Align and tighten the retaining screws. Figure 44: Installing a Fan Tray Replace a Fabric Module Replace a fabric module when needed. You need a the following tools to replace a fabric module: • ESD-preventive wrist strap •...
  • Page 68 BlackDiamond X8 Maintenance Procedures b Holding both handles, pull the fan tray straight out of the chassis. Figure 45: Removing a Fan Tray 4 Set the fan tray aside in a safe place. 5 Remove the fabric module. a Loosen the retaining screw on each inserter/extractor lever on the fabric module. BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 69 BlackDiamond X8 Maintenance Procedures b Simultaneously rotate both levers toward the ends of the module to unseat the internal connectors (Unseating a Fabric Module). Figure 46: Unseating a Fabric Module BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 70 BlackDiamond X8 Maintenance Procedures c Carefully slide the module out of the switch chassis and set it aside on an anti-static surface. Figure 47: Removing a Fabric Module 6 Install the replacement fabric module. a Remove the module from the antistatic packaging. b Loosen the screws on the insertion/extraction levers and open the levers.
  • Page 71 BlackDiamond X8 Maintenance Procedures c Align the circuit board with the guides at the top and bottom of the chassis and slide the module into the chassis. Figure 48: Installing a Fabric Module BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 72 BlackDiamond X8 Maintenance Procedures d When the levers start to engage, push them toward the module to seat the module in the chassis. e Align and tighten the retaining screws to fasten the module in place. Figure 49: Securing a Fabric Module 7 Re-install the removed fan tray.
  • Page 73: Replace A Management Module

    BlackDiamond X8 Maintenance Procedures b Align and tighten the retaining screws. Figure 50: Installing a Fan Tray Replace a Management Module You need the following tools and equipment to replace a management module: • ESD-preventive wrist strap • #2 Phillips screwdriver •...
  • Page 74 BlackDiamond X8 Maintenance Procedures 4 On the injector/ejector lever, turn the captive screw counter-clockwise until the yellow band around the screw head of is completely visible. Figure 51: Unlocking a Module 5 Squeeze the release latch on the injector/ejector handle and rotate the handle to the right (away from the module) to unseat the module from the internal connectors.
  • Page 75 BlackDiamond X8 Maintenance Procedures Holding the module by the metal rail and front panel only, remove the module from the antistatic packaging. Caution To prevent ESD damage, never touch the components on the PCB or the pins on any of the connectors.
  • Page 76 BlackDiamond X8 Maintenance Procedures 5 Use a # 2 Phillips screwdriver to lock the handle into place. When the locking screw is fully tightened, the yellow band around the screw head is completely hidden. Caution Be careful to avoid over-torquing and stripping the screw head. Figure 54: Locking the Module into Place Install a Management Module Blank Install a blank management module in every unoccupied management slot.
  • Page 77 BlackDiamond X8 Maintenance Procedures 3 Disconnect network cables from the front of the module. 4 On each injector/ejector lever, turn the captive screw counter-clockwise until the yellow band around the screw head of is completely visible. Figure 55: Unlocking a Module 5 Squeeze the release latch on each injector/ejector handle and rotate both handles outward to disconnect the internal module connectors.
  • Page 78 The shipping cover maintains the mechanical stability of the chassis during shipping. 2 Keep the shipping cover and store it with the other chassis shipping materials, in case you need to move the chassis or return it to Extreme Networks. 3 Attach the ESD-preventive wrist strap to your bare wrist.
  • Page 79 BlackDiamond X8 Maintenance Procedures 6 Verify that the module injector/ejector handles are open. Keep the injector/ejector handles in the open position as you slide the module into the chassis slot. Figure 57: Installing an I/O Module Note If the injector/ejector handles are in the latched position, they prevent the module from sliding all the way into the slot.
  • Page 80 BlackDiamond X8 Maintenance Procedures 9 Use a # 2 Phillips screwdriver to lock each handle into place. When a locking screw is fully tightened, the yellow band around the screw head is completely hidden. Caution Be careful to avoid over-torquing and stripping the screw heads. Figure 58: Locking the Module into Place Install I/O Module Blanks Switches are shipped with a reinforcement shipping cover installed over all the I/O module slots.
  • Page 81: Reseating A Management Module Dimm

    BlackDiamond X8 Maintenance Procedures 2 Align the module blank with the card guides for the open slot on the chassis. Figure 59: Installing a Module Blank 3 Use a #2 Phillips screwdriver to tighten the captive screws at each end of the module blank. a Tighten the screws of each installed module blank before inserting additional modules or blanks.
  • Page 82 BlackDiamond X8 Maintenance Procedures 3 On the injector/ejector lever, turn the captive screw counter-clockwise until the yellow band around the screw head of is completely visible. Figure 60: Unlocking a Module 4 Squeeze the release latch on the injector/ejector handle and rotate the handle to the right (away from the module) to unseat the module from the internal connectors.
  • Page 83 BlackDiamond X8 Maintenance Procedures 6 Locate the DIMM on the management module. DIMMs Figure 62: Locate the DIMM 7 Remove any glue at the top of each latch with your fingers. Glue Figure 63: Glue at the top of the DIMM latch BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 84 BlackDiamond X8 Maintenance Procedures 8 Unlock the DIMM and pull it perpendicularly straight up out of the socket. Do not twist or bend the DIMM while you are pulling it out. Figure 64: Unlock the latches on the DIMM BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 85: Pack The Chassis For Shipping

    BlackDiamond X8 Maintenance Procedures 9 Reseat the DIMM into place, pushing it gently as far as it will go into the socket (there should be a clicking sound signifying the DIMM is fully seated). When it is fully seated the latches will lock back into place.
  • Page 86 BlackDiamond X8 Maintenance Procedures Prepare the Chassis for Removal To prepare the chassis for removal from the rack, remove the installed modular components. Turn off the power to the chassis and remove the installed power supplies. a Remove the power cord retainer and disconnect all power cords. b Remove all the installed power supplies.
  • Page 87 BlackDiamond X8 Maintenance Procedures c Set the fan tray aside in a safe place. Figure 66: Removing the Fan Trays 3 Using four mounting screws, attach the support brackets to the equipment rack immediately below the chassis. 4 Remove the rack mounting screws that secure the chassis to the rack. 5 Slowly guide the chassis out of the equipment rack using the support bracket for support.
  • Page 88 BlackDiamond X8 Maintenance Procedures b Align and tighten the retaining screws. Figure 67: Installing a Fan Tray Caution Do not use the fan tray handles to lift or maneuver the chassis. The handles on the fan trays are not designed to support the weight of the chassis. 9 Remove the mid-mount brackets from the sides of the chassis.
  • Page 89 BlackDiamond X8 Maintenance Procedures Assemble the Shipping Container Once the chassis is removed, assemble the shipping container around it. At each corner, attach a restraining bolt to the shipping bracket, securing the chassis to the shipping pallet. Figure 69: Recrating the BlackDiamond X8 Chassis 2 Put the lower foam cushion around the base of the chassis and set the upper foam cap on top of the chassis.
  • Page 90 BlackDiamond X8 Maintenance Procedures 3 Set a corner brace at each corner of the chassis, and slide the shipping carton down over the chassis. Figure 71: Placing the Shipping Carton over the Chassis 4 Secure the carton to the pallet using nylon strapping. Figure 72: Shipping Carton with Nylon Straps BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 91: Chapter 8: Safety Information

    Only trained and qualified service personnel (as defined in IEC 60950-1) should install, replace, or perform service to Extreme Networks switches and their components. Warning Read the following safety information thoroughly before installing Extreme Networks products. Failure to follow this safety information can lead to personal injury or damage to the equipment.
  • Page 92: Maintenance Safety

    This system contains no customer serviceable components. Do not attempt to repair a chassis, power supply, module, or other component. In the event of failure, return the defective unit to Extreme Networks for repair or replacement, unless otherwise instructed by an Extreme Networks representative.
  • Page 93: Cable Routing For Lan Systems

    Cable Routing for LAN Systems Extreme Networks equipment meets the requirements for LAN system equipment. LAN systems are designed for intra-building installations; that is, cable runs between devices must be in the same building as the connected units, except under the conditions listed in the next paragraph.
  • Page 94 • Extreme Networks AC power supplies do not have switches for turning the unit on and off. Remove all wall plugs from the electrical outlet to disconnect the power. Make sure that these connections are easily accessible.
  • Page 95: Selecting Power Supply Cords

    Dispose of the battery in accordance with the battery manufacturer’s recommendation. Fiber Optic Ports and Optical Safety The following safety warnings apply to all optical devices used in Extreme Networks equipment that are removable or directly installed in an I/O module or chassis system.
  • Page 96: Sicherheitshinweise

    Never alter, modify, or change an optical device in any way other than suggested in this document. Note Extreme Networks optical modules are tested to work in all supported Extreme Networks switches. We recommend that all customers use Extreme Networks optical modules in their Extreme Networks switches.
  • Page 97: Überlegungen Vor Der Installation

    Versichern Sie sich, dass Ihre Netzteile den Gleichstrom- bzw. Wechselstrombedarf aller Netzwerkgeräte decken können. • Racks für Extreme Networks-Geräte müssen fest am Boden verankert werden. Bei nicht vorschriftsmäßiger Fixierung des Racks besteht die Gefahr, dass das Rack bei Wartungsarbeiten umkippt.
  • Page 98: Allgemeine Sicherheitshinweise

    Das System enthält keinerlei Teile, die vom Benutzer zu warten sind. Versuchen Sie nicht, Chassis, Netzteil, Modul oder andere Komponenten eigenmächtig zu reparieren. Senden Sie im Falle einer Störung das defekte Teil zur Reparatur oder zum Austausch an Extreme Networks ein, sofern ein Extreme Networks-Vertreter nicht etwas anderes angibt.
  • Page 99: Installation Der Netzteile Und Netzanschluss

    Sie bitte Anhang B dieser Anleitung oder dem Datenblatt für die Netzversorgung unter http:// www.extremenetworks.com. Warning Die in diesem Abschnitt aufgeführten Anforderungen müssen bei der Installation von Extreme Networks-Netzteilen und beim Netzanschluss unbedingt erfüllt werden. Bei Installation eines Netzteils: BlackDiamond X8 Series Switches Hardware Installation Manual...
  • Page 100 Der Anschluss an die Gleichspannungsquelle Ihrer Einrichtung muss von einem qualifizierten, geprüften Elektriker vorgenommen werden. • DC-Netzteile von Extreme Networks haben keinen Ein-/Ausschalter. Versichern Sie sich, dass der DC-Kreis spannungslos ist, ehe Sie das Gleichstromkabel an einer Gleichstromeingangsbuchse an- oder abstecken.
  • Page 101: Auswahl Der Netzkabel

    Im Lieferumfang von Extreme Networks-Produkten sind keine Netzkabel enthalten. Ein für Ihr Produkt und Land passendes Netzkabel erhalten Sie entweder von Ihrem zuständigen Extreme Networks Channel Account Manager oder Sales Manager oder im örtlichen Fachhandel. Die Anforderungen an das Netzkabel entnehmen Sie Anhang B zu dieser Anleitung.
  • Page 102: Lwl-Ports Und Optische Sicherheit

    Optische Geräte dürfen auf keine andere Weise als in diesem Dokument empfohlen verändert, modifiziert oder umgebaut werden. Konformität von GBIC, SFP (Mini-GBIC), QSFP+, XENPAK und XFP Steckbare optische Module von Extreme Networks und direkt angeschlossene Kabel erfüllen folgende gesetzliche Vorschriften. •...
  • Page 103: Chapter 9: Technical Specifications

    Technical Specifications BlackDiamond X8 Switch Modules for BlackDiamond X8 Switches Power Supplies for BlackDiamond X8 Switches Connector Pinouts Conformity Statements for EMC Class A BlackDiamond X8 Switch Technical specifications. BlackDiamond X8 Switch Technical Specifications Table 13: Physical Characteristics Height: 25 inches (63.5 cm) BlackDiamond X8 chassis Width: 18 inches (45.7 cm) Depth: 30 inches (76.2 cm)
  • Page 104 Technical Specifications Table 14: Safety Standards North American UL 60950-1:2007 2nd Ed. or UL 60950-1 1st Ed:2007 as applicable (US) cULus listed to CSA 22.2 No. 60950-1-07 (Canada) FCC 21 CFR 1040.10 (US Laser Safety) CDRH Letter of Approval (US FDA Approval) European/International CB Scheme, IEC 60950-1:2005, 2nd Ed.
  • Page 105: Modules For Blackdiamond X8 Switches

    Technical Specifications Table 17: IEEE 802.3 Media Access Standards Note: These standards are IEEE 802.3 10BASE-T (management port only) module-specific and may not IEEE 802.3u 100BASE-TX, 100BASE-FX (management port only) apply to every module in the IEEE 802.3z 1000BASE-X series. IEEE 802.3ab 1000BASE-T IEEE 802.3ac VLAN Tag IEEE 802.3ad Link Aggregation...
  • Page 106: Power Supplies For Blackdiamond X8 Switches

    Technical Specifications Specifications for BlackDiamond X8 Series Modules Table 20: I/O Modules 3 inches high by 17 inches wide by 18 inches deep Dimensions (7.6 cm x 43.1 cm x 45.7 cm) (all models) Note: Inserter/extractor levers add 2.25 inches (5.7 cm) to the depth measurement. BDXA-10G48X Weight: 10.9 lb (4.9 kg) Packaged weight: 15.60 lb (7.08 kg)
  • Page 107: Connector Pinouts

    Technical Specifications Table 23: Specifications for the BlackDiamond X8 AC Power Supply (Model # 48011) (continued) Physical characteristics Height: 1.5 inches (3.8 cm) Width: 4.2 inches (10.6 cm) Depth: 14.5 inches (36.8 cm) Weight: 5.3 lb (2.4 kg) Packaged weight: 6.15 lb (2.80 kg) Input Rated inputs: Low range: 100 to 120 V...
  • Page 108 Technical Specifications Table 24: RJ-45 Console Port on BlackDiamond X8 Switch Function Pin Number Direction CTS (clear to send) DTR (data carrier detect) TXD (transmit data) GND (ground) — GND (ground) — RXD (receive data) DSR (data set ready) RTS (request to send) The following table shows the pinouts for an RJ-45-to-DB-9 adapter.
  • Page 109: Conformity Statements For Emc Class A

    Technical Specifications PC-AT Serial Null-modem Cable Pinouts shows the pinouts for a 9-pin to 9-pin (PC-AT) null-modem serial cable. Figure 74: PC-AT Serial Null-modem Cable Pinouts Conformity Statements for EMC Class A International—CISPR 22 Class A This is a Class A product. In a domestic environment, this product may cause radio interference, in which case the user may be required to take adequate remedial measures.
  • Page 110 Technical Specifications Japan (VCCI Class A) This is a Class A product based on the standard of the VCCI Council. If this equipment is used in a domestic environment, radio interference may occur, in which case the user may be required to take corrective actions.
  • Page 111: Index

    Index components, installing fabric modules 50 AC power cord 23 I/O modules 56, 78 AC power supply management modules 54 features 22 module blank 58, 80 LEDs 23 power cord retainer 48 access, restricted 26 components, removing amperage, calculating for UPS 35 chassis 86 ANSI standards 36 fabric module 67 fan tray 65 management module 73, 81 power supply 62 BDX-MM1 module.
  • Page 112 Index BlackDiamond X8 chassis 7 management port 10 fabric module 19 management port location 13 management module 12, 13 mechanical recommendations for rack 27 power supplies 22 module blank, installing 58, 80 fiber optic cable module configuration, default 15 bend radius 33 modules first switch login 60 I/O 15 fuses in power supplies 23 management 13 switch fabric 19 mounting holes, rack 27, 28...
  • Page 113 Index grounding 28 selecting 35 space 28 transition time 35 restricted access 26 USB port 10, 13 RF interference UTP cable patch panel installation 32 discharge ESD 32 preventing 33 RF interference 33 safety information in German 97 weight safety requirements 91 chassis 103 safety requirements. 25 fan tray 103 service access to the rack 28 modules 106 signal quality and RF interference 33 power supply 107...

Table of Contents