PEERLESS Pinnacle PI-199 Installation, Operation & Maintenance Manual page 12

Stainless steel gas boilers
Hide thumbs Also See for Pinnacle PI-199:
Table of Contents

Advertisement

Table
1:
Natural
Gas
Model
Input
(Cubic
Ft/Hr)
PI-80
80
Pb140
140
PI 199
199
Based on 1000 Btu/Cubic Ft.
Table
2:
LP Gas
Model
Input
(Cubic Ft/Hr)
PI-80
32
PI-140
56
PI-199
79
Based on 2500 Blu/Cubic Ft.
Table 3:
Pipe Capacity
Capacity of pipe of different diameters
and lengths in cu. ft. per
hour with pressure drop of 0.3 in. and specific gravity of 0.60.
No allowance
for an ordinary number
of fiVdngs is required.
Pipe
Length
Feet
3/'4"*
Pipe
I
1 #
1¼"
1½"
I
Pipe
Pipe
Pipe
10
278
520
I
1,050
20
190
i
350
730
30
152
285
590
40
130
245
500
50
115
215
440
60
105
195
400
Multipliers to be used wi_ the above _b_
when the
specific gravity of me gas is other than 0.60:
Specific Gravity
. . .0.5
0.55
0.60
0.65
Multiplier
........
1.10
1.04
1.00
0.962
1,600
1,100
890
760
i
670
J
610
0.70
0.926
9