PEERLESS Pinnacle PI-199 Installation, Operation & Maintenance Manual page 11

Stainless steel gas boilers
Hide thumbs Also See for Pinnacle PI-199:
Table of Contents

Advertisement

2.
3.
4.
5.
6.
Size and install the gas supply piping properly in
order to provide a supply of gas sufficient to meet
the maximum
demand
without exceeding
a pressure
drop greater than .5" W.C. between the meter and
the boiler.
Determine
the volume of gas to be provided
to the
boiler in cubic feet per hour. To obtain this value,
divide the Btu per hour rating (on the boiler rating
label) by the heating value of the gas in Btu per
cubic feet. Obtain the heating value of the gas from
the gas supplier. As an alternative,
use Table 1 or 2
on the next page to obtain the volume of gas to be
provided
to the boiler.
Use the value obtained
above as the basis for piping
sizing. Size the gas piping in accordance
with Table 3
for natural gas. Consult the National Fuel Gas Code
ANSI Z223.5/NFPA
54 and/or CAN/CGA
B149 for
other sizing options and LP gas pipe sizes.
Locate the drop pipe adjacent to, but not in front of
the boiler.
Install a sediment trap. See Figure 6. Locate a tee in
the drop pipe at same elevation as the gas inlet
connection
to the boiler. Extend the drop pipe to a
pipe cap.
Install a ground joint union ahead of the gas control
assembly to permit servicing of the control. Install a
service valve as shown in Figure 6.
Use a pipe joint sealing compound that is resistant to
the action of liquefied petroleum gas. A non-resistant
compound
may lose sealing ability in the presence of
this gas, resulting in a gas leak and fire or explosion
potential.
7. Check piping for leaks prior to placing the boiler in
operation.
Use an approved
gas detector, a non-corrosive
leak
detection
fluid or other leak detection
method. If
leaks are found, turn off all gas flow and repair as
necessar_
When checking for leaks, do not use matches,
candles, open flames or other methods that provide a
source of ignition. This can ignite a gas leak,
resulting in fire or explosion.
8. The gas piping connection
to the boiler must be a
minimum
of 3/4 pipe size. Boiler is provided with a
3/4 x I/2 pipe reducer. Do not remove the reducer.
SERVICE VALVE---J_"-_
O.J. UNION _
SEDIMENT TRAP
FLOOR
LINE_
I
_
JACKET
Figure
6:
Gas Connection
to Boiler
9.
Disconnect the boiler and its individual shut-off valve
from the gas supply piping system during any
pressure testing of that system at test pressure in
excess of i/2 psig (3.5 kPa). Remove the mounting
screws of the flanged gas connection
on the gas
valve, and disconnect flange from valve.
Do not subject the gas valve to more than 112 psi
pressure. Doing so may damage the valve.
Isolate the boiler from the gas supply piping system
by closing its individual service valve during any
pressure testing of the gas supply piping system at
test pressure equal to or less than 1/2 psig (3.5 kPa).
10. Check for proper supply pressures to boiler at
sediment trap location. Remove pipe cap and
provide fittings as required. Minimum permissible
supply pressure (Inches Water Column):
Natural Gas
3.7"
LP Gas
3.7"
Maximum permissible supply pressure to the boiler
(Inches Water Column):
Natural Gas
13.5"
LP Gas
13.5"
11. Maintain a minimum distance of 10 feet between a
gas pressure regulator and boiler.
12. Gas line must be properly purged of air to allow for
normal main burner ignition.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pinnacle pi-140Pinnacle pi-80

Table of Contents