Reset Interlocking Output (H9/C3) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
32.3
Action
"Access"
Scroll to menu H9.
"A"
Scroll to menu C3.
"A"
"A"
or
"Return"
Rev: 3

Reset interlocking output (H9/C3)

All activated interlocking outputs are listed in this menu.
Interlocking output activated via its control expression and with
latching output selected (in Win128): The output has to be reset via
this sub menu (C3).
Interlocking output activated via its control expression and with
latching output not selected: The output can be reset via this sub
menu (C3).
Interlocking output activated via menu H9/C2: The output has to be
reset via this sub menu (C3).
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Reset interlocking output
Reset interlocking output
area 00 point 00
Reset interlocking output
EBL128 Operating Instructions V1.1.x
ACCEPT? H9
ACCEPT? C1
ACCEPT? C3
ACCEPT?
ACCEPT? C3
129
Comments
According to chapter
"Access", see page 78.
This is a list in which you
can scroll. If there are no
activated outputs, menu C3
will be shown again.
Press "A" (for reset) or
"Return" (no reset) to
menu C3.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.