EBL128 cannotcommunicate with the board. Check / edit the address.
Check the cables / connections.
FAULT: No reply FBP x
FBP=1826 / 1828. (Ext. Fire Brigade Panel)
EBL128 cannotcommunicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: Output Sx
This is valid for the EBL128 supervised voltage outputs S0 and S1.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for a fire brigade tx (type Routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
 Calibration not performed via menu H5/A3.
 Short-circuit / break on the connected cable / equipment.
 Blown fuse "F8" (S0) or "F6" (S1) on the main board 4556.
 Connected equipment might be "missing".
 End-of-line resistor(s) missing or not correct value (see
drawing 128-22). 1- 5 resistors 33K.
NOTE! The calibrated value has to be in the range 4K7-50K.
FAULT: Output x expansion board x
A fault on the supervised output x on the expansion board (4583) with
address x.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
 Calibration not performed via menu H5/A3.
 Short-circuit / break on the connected cable / equipment.
 Blown fuse "F1" (Output 0) or "F2" (Output 1) on the 4583
board.
 Connected equipment might be missing.
 End-of-line resistor(s) missing or not correct value (1-5 x
33K).
NOTE! The calibrated value has to be in the range 4K7-50K.