Panasonic MEW01091 Operating Instructions Manual page 19

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
LED indicator
L7
General fault (yellow)
L8
Disablements (yellow)
L9
Test mode (yellow)
L10
Door open (yellow)
12
Störung Löschanlage
(yellow)
L11
Fault tx activated (yellow)
L12
Service (yellow)
12
Leitungsstörung
Löschanlage (yellow)
L13
Fault / Disablements
Alarm devices (yellow)
L14
System fault (yellow)
L15
Fault / Disablements
Fire brigade tx (yellow)
LED indicators on the Control Panel (CP)
Indicating
Fault(s), i.e. not acknowledged fault(s) and/or
acknowledged but not corrected fault(s).
Something is disabled / disconnected via a menu or
automatically via "Single encapsulated reset"
One or more zones are in "test mode".
A door is open (in EBL128 or an ext. FBP).
An input with trigger condition "Extinguishing system
fault" is activated (true).
Output activated for Fault tx (routing equipment), i.e.
one or more not acknowledged faults.
Test of routing equipment in progress (see menu H1).
One or more sensors have reached the service level.
See menu H4/U6.
Short-circuit or cut-off (open circuit) on a supervised
input OR a supervised output type "Extinguishing".
One or more outputs (type Alarm device) are disabled.
Blinking: One or more supervised outputs (type
Alarm device) have generated fault(s).
EBL128 is not running (because of S/W, CPU or
memory fault).
Output for Fire brigade tx (routing equipment) is
disabled via menu (H2/B3) or via an open door.
Blinking: Routing equipment power supply output
or one or more supervised outputs (type Routing
equipment) have generated fault(s).
11
See also chapter "Door open", page 36.
12
L10 and L12 have different functions on the German front.
13
This is also valid when EBL128 has no "contact" with a unit with such an
output, e.g. a 3377, 3378, 3361, etc.
14
The LED is turned on during restart and stays on for restart code other
than 00 and 03 until the fault is acknowledged.
15
Main board terminal block "J1:11-12".
16
This is also valid when EBL128 has no "contact" with a unit with such an
output, e.g. an I/O unit 3361, etc.
17
EBL128 Operating Instructions V1.1.x
13
14
16
7
.
11
11
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl128

Table of Contents