XP24000 receptacle part numbers and ordering information

Table 23
lists the plug and receptacle part numbers for 60-Hz configurations of the HP XP24000 disk
array.
Table 23 XP24000 receptacle part numbers
Power source
Single-phase
Three-phase
1
The DDK 115J-AP8508 plug has the same fit and form as the Russellstoll (T&B) 3760PDG plug and is fully compatible with
Russellstoll (T&B) connectors.

XP24000 three-phase AC cabling for the USA (60 Hz)

Each three-phase DKU has two main disconnect devices (two main breakers for dual power lines) so
that AC power to the unit can be supplied from separate power distribution panels with two power
supply cords.
CAUTION:
An HP representative should be present whenever the disk array is being connected to a new power
source for the first time.

Connecting the external power supply cords

The HP XP24000 disk array is factory-configured for 30-amp, three-phase power.

30-amp, three-phase power cords

When the disk array uses 30-amp, three-phase input power, the DKC and DKUs have two power
cords each.
Breaker rating
30 A
50 A
30 A
XP24000/XP20000 Disk Array Site Preparation Guide
Plug
Russellstoll or Thomas &
Betts 3750DP
Russellstoll or Thomas &
Betts 9P53U2
1
DDK 115J-AP8508
Receptacle
Russellstoll or Thomas &
Betts 3933 (alt. 9C33U0)
or 3753 (alt. 9R33U0W)
Russellstoll or Thomas &
Betts 9C53U2 or
9R53U2W
Russellstoll 3934 (alt.
9C34U0) or 3754 (alt.
9R34U0W)