Checklist questions
Does the new floor plan include the clearance
*
required for the floor's load rating?
Is the computer room structurally complete
*
(walls, floor, air conditioning system, and so
on)?
*
Is the floor adequate for the equipment load?
Is antistatic flooring or mats installed?
Is there a dedicated analog telephone line for
the optional modem-based remote support
solution (if chosen)?
Is the infrastructure available for the default In-
ternet-based remote support solution?
Is a telephone line available for HP representat-
ive use?
Is a private LAN available?
Can the temperature be maintained between
*
16 and 32 degrees C?
Can temperature changes be held to less than
*
10 degrees C per hour?
Can the humidity level be maintained between
*
20% and 80%?
Is the computer room protected against dust,
*
pollution, and metallic particulate contamina-
tion?
Does the computer room support other environ-
*
mental considerations (such as vibration and
acoustics)?
Are two AC outlets, on different lines, available
*
for the equipment?
Does the input voltage correspond to the DKC
*
and DKU equipment specifications?
Does the input frequency correspond to equip-
*
ment specifications?
Is an appropriate uninterruptedly power supply
(UPS) strategy in place?
If lightning arresters are recommended, are they
installed?
Yes
No
XP24000/XP20000 Disk Array Site Preparation Guide
Reference
XP24000 and XP20000 floor clearance re-
quirements, page 27
Computer room
requirements, page 23
XP24000 and XP20000 floor clearance re-
quirements, page 27
Floor covering
requirements, page 26
Data communication
requirements, page 37
Data communication
requirements, page 37
Data communication
requirements, page 37
Data communication
requirements, page 37
Temperature
specifications, page 33
Temperature
specifications, page 33
Humidity
specifications, page 34
Controlling dust and
pollution, page 36
Vibration
specifications, page 34
Acoustic
requirements, page 35
Electrical
requirements, page 39
Line
voltage, page 39
XP24000 AC line voltage
requirements, page 45
Frequency, page 40
Uninterruptible Power Supply
Sources of electrical
interference, page 43
(UPS), page 42
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Storageworks xp20000Storageworks xp24000

Table of Contents