Frequency
AC Line Voltage Requirements for the HP SureStore E Disk Array XP512
42
AC line frequency is normally determined by your local power providers.
In some cases, electrical power is supplied by motor-generators. Shifts in
AC line frequency can cause system errors. Your HP CE can monitor the
frequency of the input AC line power and make recommendations, if
necessary.
The basic AC power requirements are as follows:
1-Phase 60Hz Operation
Nominal rated voltage (Vac)
Minimum operating voltage
(Vac)
Maximum operating voltage
(Vac)
Rated line current: DKU
(Arms)
Rated line current: DKC
(Arms)
Dropout carry-thru time at
minimum line voltage (ms)
60Hz-V1 60Hz-V2s 60Hz-V3
200
208
184
191
212
220
12.3
11.9
5.7
5.6
500
500
HP SureStore E Disk Array XP512: Site Prep Guide
230
212
244
10.8
5.2
500
Need help?