Power Requirements: Single Secondary Input (Primary Offline)

Reference Supplier Information

Preparing for Installation
This is based on a worst-case voltage (Vac input 10 percent) and a
maximum configuration for disk control and disk array frames. A phase
imbalance of 15 percent is also included in the calculation.
First DKU/DKC
Input (Vac)
Combination
208
25.0 A (9.0kVA)
400
16.3 A (11.3k VA) 9.9 A (6.9K VA)
American Power Conversion
32 Fairgrounds Road
West Kingston, RI 0289
Phone Numbers:
Technical Support & Product Info.
1-800-800-4272
Corporate
1-800-788-2208
1-401-789-5735
To find out more about the recommended American Power Conversion
UPS, travel to the APC web site:
www.apcc.com
You can also contact your HP service representatives for specific
configuration needs for your area.
Each Additional
DKU
15.0 A (5.4kVA)
59