Explanation of ]ump_ Settings (_o_tt_
ECON JUMPER SETTING
If the jumper
for MISC2
or M/SC3
is set
to ECON,
the corresponding
M/SC
screw
termina/
on the backp/ate
wit! be connected
to an economizer,
ECONOMIZER
OPERATION
- If your HVAC unit is equipped
with an
economizer
system, the thermostat will provide power to the MISC2 or
M]SC3 terminal of the thermostat when the thermostat
is in an occupied
time period.
The MISC2 or M]SC3 terminal wilt be de-energized
when the
thermostat
is in an unoccupied
time period.
Y2 JUMPER SETTING
If the jumper
for MISC1
is set to Y2 the M/SC1
screw
terminal
on
the backp/ate
wit/control
a
second
stage
of cooling,
Y2 OPERATION
- SECTION
13
Controt
up to two Coot
stages,
The 2nd
Stage
of cool
Ls turned
on when:
(A) The
1st Stage
has been
on for the time
required
(step
#27,
page
13.6).
It is adjustable
from
0-60
minutes
and the default
Ls two minutes,
And
(B) The
temperature
spread
from
the setpoint
is equaI
to or greater
than:
the setpoint
plus
the deadband
(step
#24,
page
13.5), plus
the 2nd deadband
(step
#25,
page
13.5).
This
2nd
deadband
is
adjustable
from
0-10
degrees
and
the default
is two degrees
I
Cooling
I
I_°°a_ba_%l_°a_ba°tl I
i
k i
(adi
1t6 ")
i _10_)
Cool
I st Stage
2nd Stage
SetpoiI_t
turn on
turn on
LTEMPE_,TUREJ--INCEASE
_
Page 21.5