Adjusting the Light Sensor
The light sensor can be adjusted for variable degrees of sensitivity.
The sensitivity adjustment screw is located on the side of the
thermostat, as illustrated below. Turning the screw clockwise
increases the sensitivity of the sensor to light.
To check for correct sensitivity, place the thermostat in the Program On
mode. When the lights are on the thermostat should enter Occupied 1
and blink the Occupied 1 icon. If the thermostat does not enter
Occupied 1 while the lights are on, use the supplied screw driver to
turn the light sensor screw clockwise until the Occupied 1 icon appears
on the display. The thermostat should enter an unoccupied period
when the lights are off. If the sensor does not enter an unoccupied
period when the lights are turned off, use the supplied screw driver to
turn the light sensor screw counterclockwise
until the Unoccupied icon
appears on the display, with the lights off.
The Light Sensor Adjustment Screw
is located on the side of the thermostat.
Light
Sensor
Adjustment
Screw
C
urn the screw clockwise
to INCREASE
light sensor
sensitivity
ill,_
Turn the screw
counter-
clockwise
to DECREASE
light
sensor
sensitivity
Due to varying lighting conditions,
light activation
may
not be suitable for all installations.