Battery Cabinet Specifications - Emerson GXT5000R-208 User Manual

With gxt5vbattw120 / gxt5vbatt battery cabinets
Table of Contents

Advertisement

BATTERY CABINET SPECIFICATIONS

MODEL NUMBER
DIMENSIONS: inches (mm)
Unit: W x D x H
Shipping: W x D x H
WEIGHT: lbs (kg)
Unit
Shipping
AC PARAMETERS – AUXILIARY AC POWER
Nominal AC Input
Nominal AC Output
Output Receptacles
BATTERY PARAMETERS
Type
Qty. x Battery Voltage x Battery Rating
Battery Mfg./ Part #
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
AGENCY
Safety
RFI/EMI
Transportation
MODEL NUMBER
DIMENSIONS: inches (mm)
Unit: W x D x H
Shipping: W x D x H
WEIGHT: lbs (kg)
Unit
Shipping
BATTERY PARAMETERS
Type
Qty. x Battery Voltage x Battery Amp Rating
Battery Mfg./ Part #
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
AGENCY
Safety
RFI/EMI
Transportation
GXT5VBATTW120
GXT5VBATTW120
16.1 x 23.6 x 5.1 (410 x 600 x 130)
23.2 x 31.1 x 12.8 (590 x 790 x 325)
121.7 (55.2)
132.3 (60.0)
208 VAC, 50/60 Hz, 400 VA, Single-Phase
120 VAC, 50/60 Hz, 400 VA, 0.75 PF (Power Factor)
5-15R (2)
Valve-regulated, nonspillable, lead acid
20 x 12 VDC x 28 watts per cell (10-minute rate)
Yuasa 28-12
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
UL 1778, c-UL Listed
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A
GXT5VBATT
GXT5VBATT
16.1 x 18.5 x 5.1 (410 x 470 x 130)
23.2 x 31.1 x 12.8 (590 x 790 x 325)
107.3 (48.7)
116.6 (52.9)
Valve regulated, nonspillable, lead acid
20 x 12 VDC x 28 watts per cell (10-minute rate)
Yuasa 28-12
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
UL 1778, c-UL Listed
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A
25

Advertisement

Table of Contents
loading

Table of Contents