Autoflush Controls
Use the LCD display, menu, and keys on the front control panel to program the autoflush controls.
7.7.2

Steam Generating Humidifier

Steam generating humidifiers are designed to operate in voltage ranges from 200 to 575 volts and
generate 11 pounds (5 kg) of steam per hour. These humidifiers operate efficiently over a wide range
of water quality conditions and automatically adjust to changes in the conductivity of water. The
humidifiers drain and refill to maintain an amperage setpoint and alert the operator when the
humidifier canister needs to be replaced. The humidifier is in the lower section of upflow units; it is in
the middle section of downflow units.

Figure 27 Steam generating humidifier

Component Operation and Maintenance
52