Specifications

General & Environmental
Units
Unit Rating
kVA
Conducted and Radiated EMC Levels
Compliant Safety Standards
Compliant Immunity Standards
Mechanical
Units
Dimensions: Width
Dimensions: Depth
In (mm)
Dimensions: Height
Environmental
Units
Operating Temperature (max)
F (C)
Relative Humidity
Maximum Operating Altitude
Ft. (M)
Nominal Heat Dissipation
BTU/Hr
Input Data
Units
Nominal Input Voltage
VAC
VAC
Power Factor
Cos 0 /
Input Frequency (nominal)
Input Frequency Range
Battery Module
Units
Battery Capacity
A/hr
Autonomy Time (full load)
Mins
Maximum Charge Current (full load)
Nominal Voltage
VDC
Recharge Time
Output Data
Units
Output Voltage
VAC
Voltage Regulation
Voltage Transient Response (100% step load)
Voltage Stability (100% step load)
Recovery Time
msec
Voltage distortion:
Output Frequency
Efficiency at 100% load
Output Overload Capability
Emerson Network Power.
The global leader in enabling Business-Critical Continuity
AC Power
Embedded Computing
Connectivity
Embedded Power
DC Power
Monitoring
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Scalable 4 - 16 kVA
4
8
kW
2.8
5.6
FCC Part 15, Class A
UL 1778; c-UL
IEEE C62.41, Category B
8 Bay
20 (508)
28 (711)
41 (1041)
4
8
32°-104° (0°-40°)
0-95% non-condensing
10,000 (3,000)
1062
2124
170 to 276
110-276 (variable, based on output load)
>.98
Hz
60
Hz
40-70
9
7
(With an equal number of Battery & Power Modules, in a non-redundant configuration)
A
3
120
Hrs
3-5 (to 90% capacity)
208/120 or 240/120
%
±3
%
±7
%
±7
96
%
<3 THD, linear load
<7 THD, non-linear load
Hz
60
%
89
%
110-125% for 10 min
126-150% for 10 sec
>151-200% for 2 cycles
.
Scalable 12 - 20 kVA
12
16
20
8.4
11.2
14
12 Bay
20 (508)
28 (711)
54 (1372)
12
16
20
3186
4248
5307
Outside Plant
Power Switching & Controls
Precision Cooling
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
SL-23900 (R03/07)
Printed in USA
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services

Surge Protection

Advertisement

loading

This manual is also suitable for:

Liebert nfinity 4-16kva