Table 10 R-134A Refrigerant Charge For Flex Pipe Connector Lines To And From Any Model; Liebert Xdo/Liebert Xdh/Liebert Xdv/Liebert Xdcf - Emerson Liebert Xtreme Density Design Manual

Xtreme density series
Table of Contents

Advertisement

Table 10
R-134a refrigerant charge for Flex Pipe connector lines to and from any model

Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF

Refrigerant Charge, lb. (kg)
Supply Line Diameter 1/2"
0.3 lb. (0.14)
0.5 lb. (0.23)
0.7 lb. (0.32)
0.8 lb. (0.36)
Return Line Diameter 5/8"
0.01 lb. (0.01)
0.02 lb. (0.01)
0.03 lb. (0.01)
0.03 lb. (0.01)
Return Line Diameter 1"
0.13 lb. (0.05)
0.2 lb. (0.09)
0.27 lb. (0.12)
0.33 lb. (0.15)
Metal Flex Pipe Connector Length
4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
4 ft. Flex Pipe existing Liebert XDV systems
6 ft. Flex Pipe existing Liebert XDV systems
8 ft. Flex Pipe existing Liebert XDV systems
10 ft. Flex Pipe existing Liebert XDV systems
4 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
6 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
8 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply
10 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert
XDV/Liebert XDCF supply