Bryant 581A Installation And Service Instructions Manual page 5

Single package rooftop electric cooling/gas heating units
Hide thumbs Also See for 581A:
Table of Contents

Advertisement

Fig. 5 — Base Unit Dimensions; 581A240
UNIT
STD. UNIT WEIGHT
581A240
1900 lbs (862 kg)
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.
Center of Gravity.
4.
Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
Rear: 7 ft-0 in. (2134) for coil removal. This dimension can be reduced to
4 ft-0 in. (1219) if conditions permit coil removal from the top.
4 ft-0 in. (1219) to combustible surfaces, all four sides (includes between
units).
Left side: 4 ft-0 in.(1219) for proper condenser coil airflow.
Front: 4 ft-0 in. (1219) for control box access.
Right side: 4 ft-0 in. (1219) for proper operation of damper and power
exhaust if so equipped.
Top: 6 ft-0 in. (1829) to assure proper condenser fan operation.
Bottom: 14 in. (356) to combustible surfaces (when not using curb).
Control box side: 3 ft-0 in. (914) to ungrounded surfaces, non-combustible.
Control box side: 3 ft-6 in. (1067) to block or concrete walls, or other
grounded surfaces.
Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/power
exhaust as stated in Note no. 6, a removable fence or barricade requires no
clearance.
8. Dimensions are from outside of corner post. Allow 0 ft-
side for top cover drip edge.
ECONOMIZER
WEIGHT
110 lbs (50 kg)
5
/
in. (8) on each
16