Bryant 524J Installation, Start-Up And Service Instructions Manual

Bryant 524J Installation, Start-Up And Service Instructions Manual

Packaged air-handling units 60 hz with puron (r-410a) refrigerant sizes 07, 08, 12, 14, 16

Advertisement

524J
Packaged Air-Handling Units
60 Hz
®
with Puron
(R-410A) Refrigerant
Sizes 07, 08, 12, 14, 16

TABLE OF CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unit Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Refrigerant Piping Access. . . . . . . . . . . . . . . . . . . . . . . 11
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . . . 15
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . . . . 16
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-33
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Motor Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Shaft Position Adjustment . . . . . . . . . . . . . . . . . . . 21
Individual Fan Wheel Adjustment . . . . . . . . . . . . . . . . 21
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . . . 22
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Replacing Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1, CL-2
Installation, Start-Up and
Service Instructions

SAFETY CONSIDERATIONS

Improper
installation,
adjustment,
maintenance, or use can cause explosion, fire, electrical shock
or other conditions which may cause personal injury or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the
individual instructions package
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and appropriate national electrical codes
(in USA, ANSI/NFPA70, National Electrical Code (NEC); in
Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol
. When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or
operation.
alteration,
service,

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 524J and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant 524J

  • Page 1: Table Of Contents

    524J Packaged Air-Handling Units 60 Hz ® with Puron (R-410A) Refrigerant Sizes 07, 08, 12, 14, 16 Installation, Start-Up and Service Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, SAFETY CONSIDERATIONS ..... . . 1 maintenance, or use can cause explosion, fire, electrical shock PRE-INSTALLATION .
  • Page 2: Pre-Installation

    PRE-INSTALLATION 1. The power supply (v, ph, and Hz) must correspond to that specified on unit rating plate. ELECTRICAL SHOCK HAZARD 2. The electrical supply provided by the utility must be suf- Failure to follow this warning could cause personal injury ficient to handle load imposed by this unit.
  • Page 3 Table 1A — 524J***A Physical Data, English — Cooling Units UNIT 524J* NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 Nominal Airflow (cfm) 2400 3000 4000 5000 6000 1800- 2250- 3000- 3750-...
  • Page 4 Table 1B — 524J***A Physical Data, SI — Cooling Units UNIT 524J* NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 Nominal Airflow (L/s) 1133 1604 1888 2360 2831 Airflow Range (L/s) 850-1416 1203-2006 1416-2360...
  • Page 5 Table 1C — 524J***H Physical Data, English — Heat Pump Units UNIT 524J* NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) 1...15 1...15 1...15 Nominal Airflow (cfm) 2400 3000 4000 Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 Nominal Motor Hp (Standard Motor)
  • Page 6 Table 1D —524J***H Physical Data, SI — Heat Pump Units UNIT 524J* NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) 1...381 1...381 1...381 Nominal Airflow (L/s) 1133 1604 1888 Airflow Range (L/s) 850-1416 1203-2006 1416-2360 Nominal Motor kW (Standard Motor) 208/230-1-60...
  • Page 7 • Right Side: 2 ft, 6 in. [762 mm] • Left Side: 2 ft, 6 in. [762 mm] • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Bryant. 5. Duct flange is factory supplied and field installed.
  • Page 8 • Right Side: 2 ft, 6 in. (762 mm) • Left Side: 2 ft, 6 in. (762 mm) • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Bryant. 5. Duct flange is factory-supplied and field- installed. UNIT WEIGHT...
  • Page 9 5 2 4 J E 1 4 A 0 0 0 A 2 0 A A A _____________ ____ Model Type Packaging 524J = Bryant Fan Coil A = Standard Puronr R--- 410A Refrigerant Not Used A = Not Used Voltage...
  • Page 10: Unit Positioning

    Unit Positioning — The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally.
  • Page 11: Unit Isolation

    Unit Isolation — distributors, and nozzles for use with R-410A. See Table 2 Where extremely quiet operation is for part numbers. Knockouts are provided in the unit corner essential, install isolators between floor and base of unit, or posts for 524J refrigerant piping. See Fig. 7, which also lists between ceiling and top section of unit.
  • Page 12 EQUALIZER LINE UPPER SENSING SPLIT BULB SOLENOID VALVE EQUALIZER LINE SIGHT GLASS 15 DIAMS AIRFLOW UPPER SENSING SPLIT BULB FILTER DIAMS SOLENOID DRIER 8 DIAMS VALVE SIGHT GLASS EQUALIZER FILTER 15 DIAMS LINE AIRFLOW DRIER SENSING LOWER DIAMS BULB SPLIT 8 DIAMS 15 DIAMS AIRFLOW...
  • Page 13 Table 2 — Factory-Installed Nozzle and Distributor Data FEEDER TUBES COIL TYPE DISTRIBUTOR NOZZLE † UNIT PER DISTRIBUTOR STD/HI EFF Qty...Part No. Qty...Part No. Qty...Part No. Qty...Size (in.) 524J*07A 4 Row 1...BBIZE-5-GA 1...1135 12... 1...G4 524J*07H 3 Row 1...BBIZE-5-GA 1...1136 15...
  • Page 14 Table 3 — Fitting Requirements (cont) ‡ ACCESS CONNECTION FITTINGS REQUIRED UNIT CIRCUIT † HOLE NO. TYPE (in.) Street Elbow Suction Lower Nipple, 7 Long Radius Elbow Street Elbow Liquid Lower Nipple, 1 Long Radius Elbow 524J*14A Street Elbow Liquid Upper Nipple, 11 Long Radius Elbow...
  • Page 15: Condensate Drain

    Condensate Drain — Install a trapped condensate drain line to unit connection as shown in Fig. 11. The unit drain con- nection is a PVC stub. See Fig. 12. Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field-supplied threaded PVC adapter.
  • Page 16: Power Supply And Wiring

    Power Supply and Wiring — Check the unit data plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch with an FAN SCROLL integrated lock-out feature of size required to provide adequate CONTACTOR fan motor starting current.
  • Page 17 Table 4 — Electrical Data, Standard Motors FAN MOTOR POWER SUPPLY VOLTAGE UNIT V*-PH-Hz Minimum LIMITS Hp (kW) MOCP Circuit Amps 208/230-1-60 187-253 1.3 (0.97) 208/230-3-60 187-253 2.4 (1.79) 524J*A07A 524J*A07H 460-3-60 414-506 2.4 (1.79) 575-3-60 518-632 1.0 (0.75) 208/230-1-60 187-253 2.4 (1.79) 11.0...
  • Page 18 Legend and Notes For Tables 4 and 5 LEGEND Determine maximum deviation from average voltage (AB) 397 – 393 = 4 v — Full Load Amps (BC) 403 – 397 = 6 v — Maximum Overcurrent Protection MOCP (AC) 397 – 396 = 1 v *Motors are designed for satisfactory operation within 10% of nominal volt- Maximum deviation is 6 v.
  • Page 19: Installation

    Table 6 — Fan Contactor Coil Data DISCHARGE CONNECTIONS — Duct flanges factory-supplied; they are shipped inside the unit attached to MAXIMUM the hairpin end of the coil tube sheet for field installation. UNIT VOLTAGE HOLDING Using the existing screws, install the duct flanges on the unit’s 524J* (vac) fan deck.
  • Page 20: Start-Up

    Fig. 18 — Duct Flange Installation START-UP Most unit service can be performed by removing one or both of the unit’s side panels. Coil cleaning or removal or insulation cleaning may require removal of a rear, top, or bottom panel, Before starting unit, check the following and correct as neces- depending on the unit’s orientation.
  • Page 21: Centering Fan Wheel

    Centering Fan Wheel — Individual Fan Wheel Adjustment — If fan and fan shaft assembly Loosen the are not properly centered, blades may scrape against the blower 2 locking bolts holding fan wheel hub to shaft. See Fig. 19. side scroll plate or may create an objectionable whistling noise. Position fan wheel in center of the fan housing and tighten It may be necessary to adjust individual fan wheels or move en- locking bolts.
  • Page 22: Fan Pulley Alignment

    Fig. 22 — Fan Rotation Fan Pulley Alignment — Align as follows: 1. Loosen setscrews on pulleys. 2. Align pulleys visually and tighten setscrews on fan pulley to lock it in place. 3. Use the methods shown in Fig. 23 to check proper pulley alignment.
  • Page 23: Replacing Filters

    Replacing Filters — Filters can be removed and in- stalled from either side of the unit. Install new filters in units that have one fan as follows: 1. Remove the side access panel (retain screws). 2. Remove the filter retainer clip (see Fig. 24). 3.
  • Page 24 Table 8A — Fan Motor Data, Standard Motor — English 524J*07A 524J*08A 524J*12A UNIT 524J*14A 524J*16A 524J*07H 524J*08H 524J*12H 208/230-1-60 Speed (rpm) 1725 1725 — — — — — — Frame (NEMA) — — — Shaft Dia (in.) — — —...
  • Page 25 Table 8C — Fan Motor Data, Standard Motor — SI 524J*07A 524J*08A 524J*12A UNIT 524J*14A 524J*16A 524J*07H 524J*08H 524J*12H 208/230-1-60 Speed (r/s) 28.75 28.75 — — — Shaft kW 0.97 1.79 — — — Frame (NEMA) — — — Shaft Dia (mm) 15.9 15.9 —...
  • Page 26 Table 9A — Standard Drive Data, 60 Hz — English 524J*07A 524J*08A 524J*12A UNIT 524J*14A 524J*16A 524J*07H 524J*08H 524J*12H MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 2.4-3.4 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) Pulley Bore (in.) Belt No.
  • Page 27 Table 9C — High-Static Drive Data, 60 Hz — English 524J*07A 524J*08A 524J*12A UNIT 524J*14A 524J*16A 524J*07H 524J*08H 524J*12H MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) †...
  • Page 28 Table 9E — Medium-Static Drive Data, 60 Hz — SI 524J*07A 524J*08A 524J*12A UNIT 524J*14A 524J*16A 524J*07H 524J*08H 524J*12H MOTOR DRIVE 86.4- 86.4- 86.4- 86.4- 94.0- Motor Pulley Pitch Diameter (mm) 111.8 111.8 111.8 111.8 119.4 Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (mm) Pulley Bore (mm)
  • Page 29 Table 10A — 524J Standard Fan Performance Data — 0.0-2.4 in. wg External Static Pressure — English EXTERNAL STATIC PRESSURE (in. wg) UNIT AIRFLOW 524J* (Cfm) 1,800 0.19 0.24 0.35 0.47 0.60 0.74 0.89 2,100 0.28 0.34 0.46 0.59 0.73 0.88 1.05 2,400...
  • Page 30 Table 10B — 524J Standard Fan Performance Data — 0-600 kPa External Static Pressure — SI EXTERNAL STATIC PRESSURE (kPa) UNIT AIRFLOW 524J* (L/s) 6.64 0.14 7.56 0.18 9.13 0.26 10.56 0.35 11.88 0.45 13.08 0.55 14.16 0.66 7.73 0.21 8.28 0.25 9.71...
  • Page 31 Table 10C — 524J High-Capacity Fan Performance Data — 0.0-2.4 in. wg External Static Pressure — English EXTERNAL STATIC PRESSURE (in. wg) UNIT AIRFLOW 524J* (Cfm) 1,800 0.21 0.26 0.37 0.49 0.63 0.77 0.92 2,100 0.31 0.37 0.49 0.62 0.77 0.92 1.09 2,400...
  • Page 32 Table 10D — 524J High-Capacity Fan Performance Data — 0-600 kPa External Static Pressure — SI EXTERNAL STATIC PRESSURE (kPa) UNIT AIRFLOW 524J* (L/s) 6.98 0.16 7.86 0.19 9.40 0.27 10.81 0.37 12.11 0.47 13.29 0.57 14.36 0.69 7.84 0.23 8.64 0.27 10.03...
  • Page 33: Service

    Legend and Notes for Tables 10A and 10C FACTORY-SUPPLIED PRESSURE DROP — ENGLISH LEGEND — Brake Horsepower Input to Fan AIRFLOW PRESSURE DROP UNIT — External Static Pressure (Cfm) (in. wg) NOTES: 1,800 0.05 1. Maximum allowable fan speed is 1200 rpm for all sizes. 524J*07A 2,400 0.08...
  • Page 34 Catalog No: II524J-04 Copyright 2009 Bryant Heating & Cooling Systems • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. Edition Date:11/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 35: Start-Up Checklist

    START-UP CHECKLIST (SPLIT SYSTEMS WITH 524J UNITS) I. PRELIMINARY INFORMATION OUTDOOR: MODEL NO. _________________________ INDOOR: MODEL NO. ___________________________ SERIAL NO. ___________________________________ SERIAL NO. ___________________________________ ADDITIONAL ACCESSORIES ______________________________________________________________________________ II. PRE-START-UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? _______________ (Y/N) ____ IF SO, WHERE: _________________________________________________________________________________________ _______________________________________________________________________________________________________ WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) _____...
  • Page 36 ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ Catalog No: II524J-04 Copyright 2009 Bryant Heating & Cooling Systems • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.