Bryant 310AAV Installation, Start-Up, Operating And Service And Maintenance Instructions

Bryant 310AAV Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage deluxe, induced-combustion 4-way multipoise gas furnace
Hide thumbs Also See for 310AAV:

Advertisement

310AAV/JAV
SINGLE- -STAGE DELUXE, INDUCED- -COMBUSTION
4- -WAY MULTIPOISE GAS FURNACE
Installation, Start- -Up Operating and
Service and Maintenance Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bottom Return Air Inlet
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Series E/F
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . .
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
4
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5
5
5
5
5
5
7
10
10
10
11
12
12
12
12
12
Use of the AHRI Certified TM Mark indicates a
12
manufacturer's participation in the program. For
verification of certification for individual products,
13
go to www.ahridirectory.org.
13
13
NOTE: Read the entire instruction manual before starting the
19
installation.
21
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1- -2009E, with permission of Nation Fire Protection
21
Association, Quincy, MA 02269 and American Gas Association,
21
Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the
22
referenced subject, which is represented only by the standard in
22
its entirely.
24
24
24
25
27
27
32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ISO 9001:2000
Always Ask For
REGISTERED
32
32
37
37
38
. . . . . . .
43
43
44
47
48
48
51
. . . . . . .
52

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 310AAV

  • Page 1: Table Of Contents

    310AAV/JAV SINGLE- -STAGE DELUXE, INDUCED- -COMBUSTION 4- -WAY MULTIPOISE GAS FURNACE Installation, Start- -Up Operating and Service and Maintenance Instructions Series E/F SAFETY CONSIDERATIONS ......General .
  • Page 2: Safety Considerations

    SAFETY CONSIDERATIONS which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used WARNING to highlight suggestions which will result in enhanced installation, reliability, or operation.
  • Page 3 [130.5] [130.5] 2 1/16 2 1/16 [51.6] [51.6] [43.5] [43.5] Ø7/8 Ø7/8 [22.2] [22.2] ACCESSORY (2) ACCESSORY (2) 8 5/8 8 5/8 [219] [219] 6 13/16 6 13/16 [172.3] [172.3] 5 7/8 5 7/8 1 15/16 1 15/16 [148.5] [148.5] 5 5/8 5 5/8 [49.2]...
  • Page 4: Introduction

    A10269 Fig. 2 --- Clearances to Combustibles chamber and/or heat exchanger. The furnace is factory- -shipped for use with natural gas. This furnace is not approved for / 27 C installation in mobile homes, recreational vehicles, or outdoors. This furnace is designed for minimum continuous return- -air temperature of 60_F (16_C) db or intermittent operation down to 55_F (13_C) db such as when used with a night setback thermostat.
  • Page 5: General Installation

    ANY WIRE CONNECTED TO THE CONTROL PRIOR National Fuel Gas Code (NFGC) NFPA DISCHARGING YOUR BODY’S 54- -2009/ANSI Z223.1- -2009 and the Installation ELECTROSTATIC CHARGE TO GROUND. Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B 2. Firmly touch the clean, unpainted, metal surface of the fur- nace chassis which is close to the control.
  • Page 6 THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND AIR CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS THE BLOWER IS LOCATED TO THE LEFT LOCATED ABOVE THE OF THE BURNER SECTION,...
  • Page 7: Air For Combustion And Ventilation

    CAUTION WARNING FIRE HAZARD PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Failure to follow this caution may result in furnace component damage. Do not install the furnace on its back or hang furnace with control compartment facing downward.
  • Page 8 f. Size openings and ducts per Fig. 7 and Table 2. WARNING g. TWO HORIZONTAL DUCTS require 1 sq./in. of free area per 2,000 Btuh (1,100 mm /kW) of combined CARBON MONOXIDE POISONING HAZARD input for all gas appliances in the space per Fig. 7 and Table 2.
  • Page 9 Table 3—Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL (1,000’S BTUH GAS INPUT RATE) (1,000’S BTUH GAS INPUT RATE) Space Volume Ft 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850 0.60 (29.7) (39.6)
  • Page 10: Installation

    The Standard Method: However, in buildings with unusually tight construction, additional air MUST be provided using the methods de- 1. The space has no less volume than 50 cu/ft. per 1,000 scribed in the Outdoor Combustion Air Method section. Btuh of the maximum input ratings for all gas appliances installed in the space and Unusually tight construction is defined as Construction with: 2.
  • Page 11: Leveling Legs (If Desired)

    NOTE: Side return- -air openings can be used in UPFLOW and 4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAR, most HORIZONTAL configurations. Do not use side return- -air or CAP or Coil Box Part No.
  • Page 12: Bottom Return Air Inlet

    If the screws are attached to ONLY the furnace sides and not the FURNACE bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment APPROVED screws are not in tension (are loaded in shear) for reliable support. COIL ASSEMBLY Platform Furnace Support COIL BOX...
  • Page 13: General Requirements

    Table 4—Opening Dimensions - - In. (mm) FURNACE PLENUM OPENING FLOOR OPENING CASING APPLICATION WIDTH Upflow Applications on Combustible or Noncombustible Floor- 12--- 11/16 21--- 5/8 13--- 5/16 22--- 1/4 ing (KGASB subbase not required) (322) (549) (338) (565) Downflow Applications on Noncombustible Flooring (KGASB 12--- 9/16 13--- 3/16 19--- 5/8...
  • Page 14 Table 5—Air Delivery - - CFM (with Filter)* FURNACE RETURN---AIR EXTERNAL STATIC PRESSURE (In. W.C.) SPEED SIZE INLET High 1035 045---08/ Bottom or Med --- High 024045 Side(s) Med --- Low High 1440 1375 1305 1240 1160 1070 045---12/ Bottom or Med --- High 1360 1300...
  • Page 15 Table 5⎯ Air Delivery - - CFM (with Filter)* (Continued) FURNACE RETURN---AIR EXTERNAL STATIC PRESSURE (In. W.C.) SPEED SIZE INLET High 2065 2000 1930 1835 1710 1590 1420 1235 1025 135---16/ Bottom or Med --- High 1790 1755 1705 1640 1550 1465 1295...
  • Page 16 " (6mm) THREADED ROD 4 REQ. OUTER DOOR A S SEMBLY SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 #8 x " (19mm) SCREWS TYPICAL FOR 2 SUPPORTS 8" (203mm) MIN FOR DOOR REMOVAL 1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED (2) HEX NUTS, (2) WASHERS &...
  • Page 17 LINE CONT A CT ONL Y PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE T OP AND TW O SIDES OF THE FURNA CE JA CKET AND BUILDING JOISTS , ″ (451mm)OVERALL STUDS , OR FRAMING. ″ (121mm) UNDER DOOR 1 ″...
  • Page 18 A02163 Fig. 19 --- Downflow Return Air Configurations and Restrictions A02162 Fig. 20 --- Horizontal Return Air Configurations and Restrictions Upflow and Horizontal Furnaces temporarily while the remaining attachment and sealing of the coil are performed. Connect supply- -air duct to flanges on furnace supply- -air outlet. Bend flange upward to 90_ with wide duct pliers.
  • Page 19: Return Air Connections

    accessories. All accessories MUST be connected to duct external with appropriate straps, hangers, etc. Use a minimum of 1 hanger to furnace casing. every 6 ft. (1.8 M) Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be WARNING resistant to the action of propane gas.
  • Page 20 Factory Factory Installed Installed Alternate Alternate Location Location 2” (51mm) Street Elbow A08551 A10291 Fig. 21 --- Burner and Manifold Fig. 23 --- Relocating J- -Box SUPPLY MANUAL SHUTOFF VALVE (REQUIRED) SEDIMENT TRAP UNION A10141 A02035 Fig. 24 --- Field- -Supplied Electrical Box on Furnace Casing Fig.
  • Page 21: 115- -V Wiring

    while swinging the front edge of the J- -Box outboard of the WARNING casing. 2. Cut wire tie on loop in furnace wires attached to J- -box. ELECTRICAL SHOCK AND FIRE HAZARD 3. Move J- -Box to desired location. Failure to follow this warning could result in personal 4.
  • Page 22: Power Cord Installation In Furnace J- -Box

    Table 7—Electrical Data MAXIMUM MAXIMUM OPERATING VOLTAGE VOLTS--- MINIMUM MAXIMUM UNIT WIRE FUSE OR RANGE FURNACE SIZE HERTZ--- WIRE LENGTH FT. CKT BKR UNIT AMPS AMPACITY# PHASE GAUGE (M)‡ AMPS† Maximum* Minimum* 045---08/024045 115--- 60--- 1 7.26 49 (14.9) 045---12/036045 115--- 60--- 1 9.79 37 (11.2)
  • Page 23 TWINNING AND/OR COMPONENT TEST BLOWER OFF-DELAY TERMINAL J2 JUMPER BLOWER OFF-DELAY HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) 24-V THERMOSTAT TERMINALS TRANSFORMER 24-VAC CONNECTIONS TEST/TWIN 0.5 AMP@24VAC 3-AMP FUSE FUSE 3-AMP SEC-2 SEC-1 LED OPERATION & EAC-2 DIAGNOSTIC LIGHT PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR 115-VAC(L2)NEUTRAL CONNECTIONS...
  • Page 24: 24- -V Wiring

    24- -V WIRING WARNING Make field 24- -v connections at the 24- -v terminal strip. (See Fig. 25.) Connect terminal Y as shown in Fig. 26 for proper cooling CARBON MONOXIDE POISONING HAZARD operation. Use only AWG No. 18, color- -coded, copper thermostat wire.
  • Page 25: Masonry Chimney Requirements

    1. If a vent (common or dedicated) becomes blocked, the fur- 1. Vent connector is Type- -B double- -wall, and nace will be shut off by the draft safeguard switch located 2. This furnace is common vented with at least 1 draft hood on the vent elbow.
  • Page 26 A10133 Fig. 27 --- Chimney Inspection Chart...
  • Page 27: Appliance Application Requirements

    APPLIANCE APPLICATION REQUIREMENTS The vent connector can exit the cabinet of the furnace through one of 5 locations. Appliance operation has a significant impact on the performance 1. Attach the single wall vent connector to the furnace vent of the venting system. If the appliances are sized, installed, elbow, and fasten the vent connector to the vent elbow adjusted, and operated properly, the venting system and/or the with at least two field- -supplied, corrosion- -resistant, sheet...
  • Page 28 Table 8—Exterior Masonry Chimney Fan + Nat Installations with Type- -B Double Wall Vent Connectors ENFPA & AGA Combined Appliance Maximum Input Rating in Thousands of Btuh per Hour INTERNAL AREA OF CHIMNEY VENT HEIGHT SQ. IN. (SQ. MM) FT. (M) (7741) (12258) (18064)
  • Page 29 Table 10—Minimum Vent Heights Caution!! for the following applications, use the minimum vertical vent heights as specified below. For all other applications, follow exclusively the national fuel gas code. MINIMUM VENT MINIMUM VERTICAL VENT FURNACE VENT FURNACE DIAMETER HEIGHT ORIENTATION ORIENTATION INPUT (BTUH/HR) IN.
  • Page 30 SEE NOTES: 1,2,4,5,6,7,8,9,10 SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures on the page following these figures A03210 A03207 Fig. 30 --- Downflow Application- -Vent Elbow Up then Left Fig. 32 --- Downflow Application- -Vent Elbow Left then Up SEE NOTES:1,2,3,4,5,7,8,9 SEE NOTES: 1,2,4,5,7,8,9 on the page following on the page following...
  • Page 31 SEE NOTES: 1,2,4,7,8,9 on the page SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures following these figures A03214 A03218 Fig. 35 --- Horizontal Left Application- -Vent Elbow Right Fig. 38 --- Horizontal Right Application- -Vent Elbow Right then Up SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures SEE NOTES: 1,2,4,5,7,8,9 on the page...
  • Page 32: Start- -Up, Adjustment, And Safety Check

    START- -UP, ADJUSTMENT, AND SAFETY CHECK Step 1 —General 3. To Begin Component Self- -Test: Remove blower access door. Disconnect the thermostat R lead from the furnace WARNING control board. Manually close the blower door switch. Short (jumper) the COM- -24v terminal on control to the TEST/TWIN 3/16- -inch quick connect terminal on control FIRE HAZARD until LED goes out (approximately 2 sec).
  • Page 33 d. Turn gas valve ON/OFF switch to ON. CAUTION e. Manually close blower door switch. f. Set thermostat to call for heat. FURNACE DAMAGE HAZARD g. Jumper R and W thermostat connections on furnace control board to start furnace. Failure to follow this caution may result in reduced furnace h.
  • Page 34 WARNING CAUTION FURNACE OVERHEATING HAZARD ELECTRICAL SHOCK HAZARD Failure to follow this caution may result in reduced furnace Failure to follow this warning could result in personal life. injury or death. Recheck temperature rise. It must be within limits specified Disconnect 115- -v electrical power and install lockout tag on the rating plate.
  • Page 35 A08411 Fig. 41 --- Wiring Diagram...
  • Page 36 BURNER ORIFICE A93059 A06666 Fig. 43 --- Orifice Hole Fig. 42 --- Gas Control Valve THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.) HOOK-AROUND AMMETER R Y W G 10 TURNS FROM UNIT 24-V CONTROL TERMINALS 0.5 AMPS FOR THERMOSTAT EXAMPLE: 5.0 AMPS ON AMMETER...
  • Page 37: Adjustments

    Step 4 —Check Safety Controls 3. Check Pressure Switch This control proves operation of the draft inducer blower. The flame sensor, gas valve, and pressure switch were all checked a. Turn off 115- -v power to furnace. in the Start- -up procedure section as part of normal operation. b.
  • Page 38 Table 13—Gas Rate (cu ft./hr) SIZE OF TEST DIAL SIZE OF TEST DIAL SECONDS FOR 1 SECONDS FOR 1 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft REVOLUTION REVOLUTION 1800 1636 1500 1385...
  • Page 39 Table 15—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated data based on 22,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) SPECIFIC GRAVITY OF NATURAL GAS AVG. GAS ALTITUDE RANGE HEAT VALUE 0.58 0.60...
  • Page 40 Table 15–Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Continued) (Tabulated data based on 22,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) SPECIFIC GRAVITY OF NATURAL GAS AVG. GAS 0.58 0.60 0.62...
  • Page 41 Table 16—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated data based on 21,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) SPECIFIC GRAVITY OF NATURAL GAS ALTITUDE AVG. GAS 0.58 0.60 0.62...
  • Page 42 Table 16—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Continued) (Tabulated data based on 21,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) SPECIFIC GRAVITY OF NATURAL GAS AVG. GAS ALTITUDE HEAT VALUE 0.58...
  • Page 43: Service And Maintenance Procedures

    SERVICE If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After status code recall is completed component test will occur. LED CODE STATUS CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
  • Page 44: Care And Maintenance

    The control system also requires an earth ground for proper For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on operation of the control and flame- -sensing electrode. this equipment. Consult your local dealer about proper frequency The 24- -v circuit contains an automotive- -type, 3- -amp.
  • Page 45 6. Remove 2 screws holding blower assembly to blower CAUTION deck and slide blower assembly out of furnace. 7. Clean blower wheel and motor using a vacuum with soft brush attachment. Blower wheel blades may be cleaned CUT HAZARD with a small paint or flux brush. Do not remove or disturb Failure to follow this caution may result in personal injury.
  • Page 46 NOTE: If thermostat terminals are jumpered at the time blower Inducer assembly and elbow need not be removed from collector box. access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle. 7. Disconnect gas line from gas manifold. c.
  • Page 47: Sequence Of Operation

    i. Install NOx baffles (if removed). 14. Reinstall internal vent pipe, if applicable. 1-7/8 15. Reinstall vent connector on furnace vent elbow. Securely (47.6 mm) fasten vent connector to vent elbow with 2 field- -supplied, corrosion- -resistant, sheet metal screws located 180_ apart. 16.
  • Page 48: Wiring Diagrams

    d. Flame- -Proving- - When the burner flame is proved at energized the furnace control CPU will continue to turn on the flame- -proving sensor electrode FSE, the furnace the blower motor BLWM at HEAT speed, and begin a control CPU begins the blower- -ON delay period and heating cycle.
  • Page 49 Fig. 49 --- Troubleshooting Guide...
  • Page 51: Accessory Listing

    Table 17—Accessory List DESCRIPTION PART NUMBER NOTES FILCABXX0016 Filter cabinet 16” (406 mm) for 4” (102 mm) wide filter Media Filter Cabinet FILCABXX0020 Filter cabinet 20” (508 mm) for 4” (102 mm) wide filter FILCABXX0024 Filter cabinet 24” (610 mm) for 4” (102 mm) wide filter FILXXCAR0016 Filter Cartridge replacements for FILCAB media cabinet Cartridge Media Filter...
  • Page 52: Parts Replacement Information Guide

    TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or classified section of your local telephone directory under “Heating Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact: BRYANT HEATING & COOLING SYSTEMS Consumer Relations Department P.O.

This manual is also suitable for:

310javStart-up and

Table of Contents