NOTE: When compressors are rotating in the wrong direc-
tion, the unit will have increased noise levels and will not
provide heating and cooling.
After a few minutes of reverse operation, the scroll compres-
sor internal overload protection will open, which will acti-
vate the unit's lockout and requires a manual reset. Reset is
accomplished by turning the thermostat on and off.
VI. INTERNAL WIRING
Check all electrical connections in unit control boxes; tighten
as required.
VII. CRANKCASE HEATER(S)
Crankcase heater(s) is energized as long as there is power to
the unit and the compressor is not operating.
IMPORTANT: Unit power must be on for 24 hours prior to
start-up. Otherwise, damage to compressor may result.
VIII. EVAPORATOR FAN
Fan belt and variable pulleys are factory-installed. Remove
tape from the fan pulley. See Tables 3-10 for Fan Perfor-
mance Data. Be sure that fans rotate in the proper direction.
See Table 11 for air quantity limits. See Table 12 for Evapo-
rator Fan Motor Specifications. See Table 13 for static pres-
sure information for accessories and options. See Table 14 for
fan rpm at various motor pulley settings. To alter fan perfor-
Table 3 — Fan Performance — 581A155225 (Low Heat Units with Standard Indoor Fan Motor)
CFM
0.2
Rpm
Watts
Bhp
3750
753
915
1.05
4000
755
991
1.14
4250
788
1129
1.30
4500
822
1280
1.47
4750
857
1443
1.66
5000
891
1620
1.86
5250
927
1810
2.08
962
2014
2.32
5500
5750
998
2233
2.57
1035
2466
2.84
6000
CFM
1.2
Rpm
Watts
Bhp
3750
1226
1971
2.27
4000
1240
2116
2.43
1255
2274
2.61
4250
4500
1272
2444
2.81
1291
2628
3.02
4750
5000
5250
5500
5750
6000
LEGEND
Bhp
— Brake Horsepower
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Standard low-medium static drive range is 834 to 1064 rpm. Alternate
high-static drive range is 1161 to 1426. Other rpms require a field-
supplied drive.
NOTES:
1. Maximum continuous bhp for the standard motor is 3.13. The maxi-
mum continuous watts is 2700. Do not adjust motor rpm such that
motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Rpm
Watts
Bhp
838
1066
1.23
865
1198
1.38
894
1341
1.54
923
1497
1.72
953
1666
1.92
984
1847
2.12
1015
2043
2.35
1047
2252
2.59
1080
2476
2.85
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Rpm
Watts
Bhp
1311
2218
2.55
1322
2366
2.72
1335
2526
2.91
1350
2700
3.10
mance, see Evaporator Fan Performance Adjustment section
on page 26.
1
NOTE: A 3
/
-in. bolt and threaded plate are included in the
2
installer's packet. They can be added to the motor support
channel below the motor mounting plate to aid in raising the
fan motor.
IX. CONDENSER FANS AND MOTORS
Condenser fans and motors are factory set. Refer to Con-
denser-Fan Adjustment section (page 27) as required. Be
sure that fans rotate in the proper direction.
X. RETURN-AIR FILTERS
Check that correct filters are installed in filter tracks (see
Table 1). Do not operate unit without return-air filters.
XI. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens must be in place before operating
unit.
XII. ACCESSORY ECONOMIZER ADJUSTMENT
Remove filter access panel. Check that outdoor-air damper is
closed and return-air damper is open.
Economizer operation and adjustment are described in Base
Unit Operation section on page 24, and in Economizer
Adjustment section on page 28.
0.6
Rpm
Watts
Bhp
Rpm
945
1278
1.47
1044
968
1414
1.63
1063
992
1562
1.80
1084
1017
1722
1.98
1106
1044
1896
2.18
1130
1071
2082
2.39
1154
1099
2282
2.62
1180
1129
2496
2.87
1.6
Rpm
Watts
Bhp
Rpm
1391
2474
2.85
1401
2623
3.02
2. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 13 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the full
bhp and watts range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.
—15—
0.8
1.0
Watts
Bhp
Rpm
Watts
1500
1.73
1138
1731
1639
1.89
1154
1873
1791
2.06
1172
2029
1956
2.25
1191
2196
2133
2.45
1212
2377
2323
2.67
1234
2572
2528
2.91
1.8
2.0
Watts
Bhp
Rpm
Watts
Bhp
1.99
2.15
2.33
2.53
2.73
2.96
Bhp

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents