Installing The Switch On The Shelf Brackets - Cisco AJ732A - MDS 9134 Fabric Switch Installation Manual

Cisco mds 9100 series hardware installation guide (ol-17951-02, february 2009)
Hide thumbs Also See for AJ732A - Cisco MDS 9134 Fabric Switch:
Table of Contents

Advertisement

Cisco MDS 9000 Family Telco and EIA Shelf Bracket
S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m
Attach the crossbar to the shelf brackets as shown in
Step 4
Insert the slider rails into the shelf brackets as shown in
Step 5
rack-mounting rails using a minimum of four 12-24 or 10-24 screws.

Installing the Switch on the Shelf Brackets

This section provides general instructions for installing the switch on top of the shelf brackets. For
detailed installation instructions, see the
page
This unit is intended for installation in restricted access areas. A restricted access area can be
Warning
accessed only through the use of a special tool, lock and key, or other means of security.
Statement 1017
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1030
Before you install, operate, or service the system, refer to the Regulatory Compliance and Safety
Note
Information for the Cisco MDS 9000 Family for important safety information.
To install the switch on top of the shelf brackets, follow these steps:
Verify that the shelf brackets are level and securely attached to the rack-mounting rails, the crossbar is
Step 1
securely attached to the shelf brackets, and the rack is stabilized.
Slide the switch onto the shelf brackets, ensuring that it is squarely positioned.
Step 2
Attach the switch to the rack-mounting rails. See the
Step 3
on page
We recommend grounding the chassis, even if the rack is already grounded. A grounding pad with two
Caution
threaded M4 holes is provided on the chassis for attaching a grounding lug.
Note
The grounding lug must be NRTL listed and compatible with copper conductors. Only copper conductors
(wires) must be used and the copper conductor must comply with National Electrical Code (NEC) for
ampacity.
Cisco MDS 9100 Series Hardware Installation Guide
A-8
2-5.
2-5.
Figure
A-2, using the 10-32 screws.
Figure
A-2. Then attach them to the rear
"Installing the Switch in a Cabinet or Rack" section on
"Installing the Switch in a Cabinet or Rack" section
Appendix A
Cabinet and Rack Installation