Warnings, Cautions, and Notices Read this manual thoroughly before operating or servicing this unit. Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows: Indicates a potentially hazardous situation which, WARNING...
NOTICE Risk of Battery Exploding! Failure to follow instructions below could cause the battery to explode resulting in equipment damage. Do NOT use a non-compatible battery with the controller! It is critical that a compatible battery be used. Risque d’Explosion de la Pile! Le non-respect des instructions qui suivent pourrait provoquer l’explosion de la pile et des dégâts à...
Page 4
Table 1. Tracer SC+ specifications (continued) Operating Environment Humidity: Between 10% to 90% (non-condensing) Product weight 1 kg (2.2 lb.) Altitude: Maximum 2,000 m (6,500 ft.) Installation: Category 3 Pollution Degree 2 Mounting the Tracer SC+ • The mounting location must meet the temperature and humidity specifications as outlined in Table •...
Page 5
Removing or Repositioning the Tracer SC+ To remove or reposition the Tracer® SC+ from a DIN rail: 1. Insert a screwdriver into the slotted release clip and gently pry upward on the clip with the screwdriver, OR; If the screwdriver fits the slot size, insert the screwdriver into the slotted release clip and rotate it to the left or right to release tension on the clip.
Page 6
Wiring and Applying Power The Tracer® SC+ controller can be powered in one of three ways: • 24 Vac @ 30 VA Class 2 Transformer with 4-position terminal block. • Output: 600A at 24 Vdc @ 50C • Tracer plug-in power supply with single barrel connector. •...
Page 7
draw for all the components connected to the SC+. If the sum exceeds 600mA, use a PM014 module or a plug-in power supply. • Tracer plug-in power supply • Using the values from Table 2, add together the current draw for all the components connected to the SC+.
Page 8
Important: This device must be grounded for proper operation! The factory-supplied ground wire must be connected from any chassis ground connection on the device to an appropriate earth ground. Note: The Tracer SC+ is NOT grounded through the DIN rail connection. 4.
Page 9
Figure 3. Apply power using a class 2 transformer...
Page 10
Figure 4. Apply power using a PM014 power supply module Service Parts Table 3. Hardware and bundles Service Part # Part Number Description KIT18461 X13651695001 TRACER® SC HARDWARE KIT18461 X13651695002 TRACER® SC and 1YR SMP KIT18461 X13651695003 TRACER® SC and 3YR SMP KIT18461 X13651695004 TRACER®...
Page 11
PM014 24 Vac TO 1.4A 24 Vdc PLU1323 X13770352001 PLUG-IN POWER SUPPLY KIT18458 X13651698001 TRACER USB LON MODULE MOD01786 X1365152401 TRANE BACNET TERMINATOR (TBT) MOD02953 X13651703001 TRACER USB WIFI MODULE KIT18459 X13690281001 MICRO SD CARD Table 5. Enclosures Service Part #...
Page 12
Front Tracer SC+ Use either IMC connection BACnet- BACnet Terminator 24 Vac/Vdc (red wire) BACnet+ Ground (black wire) Agency Listings and Compliance The European Union (EU) Declaration of Conformity is available from your local Trane® office.
Page 13
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
Need help?
Do you have a question about the Tracer SC+ and is the answer not in the manual?