Connecting to the Alarm Port

Connecting to the Alarm Port

Connect to the alarm port as follows:
Step 1
Insert the three-pin alarm port connector into the alarm port terminal block. (See
Figure 3-13 Connecting to the Alarm Port
Note
Strip a minimum 1/4 in. (0.625 cm) off the wire insulation to connect the stranded wires to the alarm
Step 2
connector. The maximum insulation strip length is 0.31 in. (0.78 cm).
Step 3
Secure the wires to the alarm connector with screws.
Caution
The maximum tightening torque on the screws is 7 in.-lb (0.79 N-m).
Connect the wires to strain relief clamps that are inserted into the holes in the ventilation grid.
Step 4
Note
Cisco AS5400 Universal Gateway Chassis Installation Guide
3-12
#1
#3
Cable ties
#2
Connect the alarm port only to a safety extra-low voltage (SELV) source using 22
AWG, or thicker, copper wire. SELV ratings are maximum 30 Volts AC (RMS),
maximum 60 Volts DC, and maximum 50 VA Power. The alarm port is rated for 2.0
Amp maximum current.
See Appendix C
"Cabling Specifications"
pinouts.
Chapter 3
Installing the Cisco AS5400 and Cisco AS5400HPX Universal Gateways
Alarm port
connector
for alarm port cable assembly and port
Figure
3-13.)
OL-2847-02 0A