11.4

General limiter

N.X1
N.X2
You can select a general limiter function.
The limitation function overrides the normal control function of the controller.
See Section 11.4.2 for this function.
11.4.1 Enable function
Assign an input to the function to enable this function.
Main menu > Commissioning > Extra configuration > Controller 1...3 > Inputs >
Operating line
General limit controller
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1...3 > General limiter >
Operating line
Limit value high
Limit value low
Differential high
Differential low
Reduction min
limitation cooling
P-band Xp
Integral action time Tn
Main menu > Controller 1...3 >
Operating line
Actual value general limiter
Switching and monitoring device RMS705B
Universal controller
Adjustable values / Comment
---, N.X1, N.X2, ..., internal analog
(analog values only)
Enable general limitation.
Range
Factory setting
(dependent on
(type-dependent)
selected type)
35.0 °C
16.0 °C
0...100 K
50 K
0...100 K
50 K
0...10 K
0.0 K
15 K, 10 %, 5 g/kg, 10 kJ/kg,
100 W/m2, 50 m/s, 10 bar,
50 mbar, 50 Pa, 100 ppm, 10.0, 50
00.00...60.00 m.s
01.00 m.s
Comment
CE1P3124en