Tranquility ® (TT) Series Table of Contents Model Nomenclature Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Horizontal Installation Vertical Installation Piping Installation Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications Ground-Water Heat Pump Applications Water Quality Standards Electrical - Line Voltage Electrical - Power Wiring Electrical - Power &...
Page 2
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
Page 8
(e.g. louvered door). Therefore, fi lter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
(e.g. louvered door). Therefore, fi lter rails are the industry Internally insulate return transition duct to reduce noise standard and are included on ClimateMaster commercial Rev.: 2/13 heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
Page 12
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
Optional pressure-rated hose assemblies designed specifi cally for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Figure 11: Supply/Return Hose Kit Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.
Hose kits are available from ClimateMaster in different treatment and fi ltering will be necessary. confi gurations as shown in Figure 12 for connection between the unit and the piping system.
Rev.: 3/22/2012 The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. When water properties are outside of those requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger.
Figure 17 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 60°F [15.6°C] must include the optional water/refrigerant circuit insulation package to prevent internal condensation.
Accessory Connections typical slow closing water control valve wiring for Taco A terminal paralleling the compressor contactor coil 500 series (ClimateMaster P/N AVM) and Taco SBV has been provided on the CXM/DXM control. Terminal series valves. Slow closing valves take approximately “A”...
Page 25
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
IOM and or unit wiring diagram. Practically back plate against the wall so that it appears level and any heat pump thermostat will work with ClimateMaster so the thermostat wires protrude through the middle units, provided it has the correct number of heating and cooling stages.
Normal mode Open Cycle (closed 5 sec, ClimateMaster technical services. Normal mode with UPS Flashing Code 8 open 25 sec) Not Clipped = 30°F [-1°C]. Clipped = 10°F DXM is non-functional...
Page 35
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
The DXM control board will bring the unit on in 2nd Stage cooling/heating modes are like any other ClimateMaster Heating. When the call is satisfi ed at the thermostat WSHP. The reversing valve (“O” signal) is energized in...
Page 39
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
4. Verify that all strainers are in place (ClimateMaster The manufacturer will not be responsible or liable recommends a strainer with a #20 stainless steel for damages from water leaks due to inadequate or wire mesh).
Page 43
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 3 0 ( T T ) S e r i e s ®...
If temperature is within 5. Two factors determine the operating limits range, proceed with the test. If temperature is of ClimateMaster heat pumps, (a) return air outside of the operating range, check refrigerant temperature, and (b) water temperature. When any pressures and compare to table 11.
97B0075N05 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi...