Appendix A: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each
circuit. The following table lists NAC wiring requirements for the HPF24S6 and HPF24S8 Field
Charger Power Supply.
Max.
NAC
allowable
Load
total loop
(Amps)
resistance
(ohms)
0.25
12.80
0.5
6.40
0.75
4.27
1.0
3.20
1.25
2.56
1.5
2.13
1.75
1.83
2.0
1.60
2.25
1.42
2.5
1.28
2.75
1.16
3.0
1.07
Table A.1 NAC Wiring Requirements for Power Supply
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National
Electrical Code (2005 Edition) Table 8, Conductor Properties.
42
CLASS-B
Max. allowable wire pair length (feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
3316
2085
1309
1658
1042
654
1105
695
436
829
521
327
663
417
262
553
347
218
474
298
187
415
261
164
368
232
145
332
208
131
301
190
119
276
174
109
Max. allowable wire pair length (feet)
AWG 18
AWG 12
AWG 14
solid
solid
solid
824
1658
1042
412
829
521
275
553
347
206
415
261
165
332
208
137
276
174
118
237
149
103
207
130
92
184
116
82
166
104
75
151
95
69
138
87
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
CLASS-A
AWG 16
AWG 18
solid
solid
654
412
327
206
218
137
164
103
131
82
109
69
93
59
82
51
73
46
65
41
59
37
55
34