5.7 Canadian Applications
Canadian applications, per ULC, require the following:
The HPF24S power supply must be used as a Notification Appliance Circuit extender only.
The TB2 terminals cannot be configured as auxiliary power outputs.
The host FACP must monitor for all ground fault conditions. The Ground Fault Detection
circuit on the HPF24S power supply must be disabled by cutting jumper JP1.
the negative (-) battery terminal of the HPF24S power supply must be connected to the
negative (-) battery terminal of the host FACP.
Battery -
HPF24S Power Supply
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
NAC Outputs only
Cut JP1
*If the SLC device does not match the one in this figure,
refer to the SLC manual appendix, which contains wiring
conversion charts for type V and type H modules.
Battery -
Host FACP
Applications