Installation; Mounting; Preventing Water Damage; Wire Routing - Honeywell Gamewell FCI GFPS-9 Installation Manual

Supplementary notification appliance circuit module
Table of Contents

Advertisement

GFPS-9 Supplementary Notification Appliance Circuit Installation Manual
Section 4

Installation

Before installing the GFPS-9, the AC input must first be wired into the building's main electrical power through
the TB1 terminals (see Figure 4-2). Shut off the electrical power to the GFPS-9, and then complete the general
installation of the GFPS-9 using the information in this section.
4.1

Mounting

Mount the GFPS-9 in locations that meet the following temperature and humidity requirements. Do not expose
the panel to conditions outside these ranges. For use in indoor, dry environments.
Temperature
Humidity
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture is expected, first attach a piece of 3/4-inch plywood to the concrete surface. Attach the
GFPS-9 to the plywood.
4.1.1

Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.2

Wire Routing

To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from
high current output and power-limited wiring. Induced noise can interfere with telephone communication or even
cause false alarms. Avoid pulling a single multiconductor cable for the entire system. Instead, separate high
current input/output from low current. Separate power-limited from non-power-limited wiring.
Non-power-limited wiring must be enclosed in conduit.
Wiring within the cabinet should be routed around the perimeter of the cabinet. It should not cross the printed
circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from
o
o
o
o
0
C-49
C (32
F-120
F)
o
o
10%-93% at 30
C (86
F) noncondensing
4-5

Advertisement

Table of Contents
loading

Table of Contents