UL Power-limited Wiring Requirements

2.1.5 In a BB-200 Cabinet
The ACPS-610 mounts in a BB-200 cabinet with four 100 amp-hour batteries (two on the top shelf
and two on the bottom). The power supply is fastened directly to the unpainted section of the
backbox with two keps nuts.
WARNING: Heavy Load!
!
The total weight of a fully loaded BB-200 will exceed 300 pounds. Additional support may be required
when mounting this cabinet to a wall.
See BB-100/200 Cabinet Installation Instructions for more information.
2.2 UL Power-limited Wiring Requirements
Power-limited wiring must remain separated from nonpower-limited wiring by at least
0.25 in. (6.4 mm), and must enter the enclosure through different knockouts. Install tie wraps and
adhesive squares to secure the wiring. Figures 2.7 and 2.8 show samples of power-limited and
nonpower-limited wiring configurations in different cabinets.
ACPS-610/E Manual — P/N 53018:A1 07/31/2007
Fasten the ACPS-610 chassis to the backbox using the two
# 4-40 keps nuts, included, (P/N 36045) at these positions.
Figure 2.6 BB-200 Mounting