2: How To Calculate System Current Draw - Honeywell HPF24S8 Installation Manual

Field charger/power supply
Hide thumbs Also See for HPF24S8:
Table of Contents

Advertisement

Calculating the System Current Draw
Secondary refers to the power supply's backup batteries.
All currents are given in amperes (A). Table 6.2 shows how to convert milliamperes and
microamperes to full amperes.
To convert...
Milliamperes (mA) to
amperes (A)
Microamperes (A) to
amperes (A)
6.3.2 How to Calculate System Current Draw
Use Table 6.3 on page 40 to calculate current draws as follows:
1.
Enter the quantity of devices in all three columns.
2.
Enter the current draw where required. Refer to the Device Compatibility Document for
compatible devices and their current draw.
3.
Calculate the current draws for each in all columns.
4.
Sum the total current for each column.
5.
Copy the totals from Column 2 and Column 3 to Table 6.3 on page 40.
Following are the types of current that can be entered into Table 6.3 on page 40
– Calculation Column 1 - The primary supply current load that the power supply must
support during a non-fire alarm condition, with AC power applied
– Calculation Column 2 - The primary supply current load the power supply must support
during a fire alarm condition, with AC power applied
– Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
Multiply
mA x 0.001
A x 0.000001
Table 6.2 Converting to Full Amperes
Power Supply Requirements
Example
3 mA x 0.001 - 0.003 A
300 A x 0.000001 = 0.0003 A
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf24s6Hpf24s6eHpf24s8eHpf24s6cHpf24s8c

Table of Contents