DIP Switch Settings

3.1 DIP Switch Settings
The following table lists the HPF24Sprogrammable features and the switch settings required to
select a particular feature. A detailed description of each feature is presented in the following
pages.
SW1 DIP Switch
1
This switch works in conjunction with switch 2 to determine the Strobe Synchronization Type
2
1 OFF, 2 OFF = no sync (steady +24V) - default
1 OFF, 2 ON = System Sensor
1 ON, 2 OFF = Gentex
1 ON, 2 ON = Wheelock
3
HPF24S configured for Slave Synchronization
4
Delay AC Fail Reporting for 2 Hours - default
Aux. Trouble Relay responds to all troubles.
Internal trouble contact responds to AC loss
5
This switch works in conjunction with switch 6 to determine Input to Output functions
6
5 OFF, 6 OFF = General Alarm - default
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Sync Input is ignored.
• HPF24S configured as Slave (switch 3 ON), NAC Outputs 1 through 4
Sync Input is monitored
• Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 & 10. Control Input #2
determines if reset will occur (must go from On to Off for a 6 second reset to occur).
• Output #4 function follows DIP switch 8 setting.
5 OFF, 6 ON = Split Alarm
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 & 2 are controlled by Control Input #1 and
Outputs 3 & 4
• HPF24S configured as Slave
Outputs 3 & 4
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
5 ON, 6 OFF = Split Temporal
• HPF24S configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2 and Control
Input #2 controls Outputs 3 & 4
ignored. HPF24S configured as Slave (switch 3 ON), Control Input #1 controls NAC Outputs 1 & 2 and
Control Input #2 controls Outputs 3 & 4
is monitored for Outputs 1 & 2
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
5 ON, 6 ON = Selective Silence
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Sync Input is ignored.
• HPF24S configured as Slave (switch 3 ON), NAC Outputs 1 through 4
Sync Input is monitored
• Control Input #2 determines when Selective Silence for all outputs will occur
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
7
Disable Charger
8
Output Circuit #4 = Door Holder
1
Strobe Synchronization only works with non-coded NACs.
2
If Door Closer function is selected (switch 8 ON), Output 4 does not function as an NAC, therefore sync input is ignored for it.
3
If no synchronization is selected by switches 1 & 2, the Sync Input is ignored.
4
Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning off the strobe.
5
When using Split Alarm with power supply configured in Slave Mode, System Sensor can not be used (Use System Sensor with
Master Mode only).
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
ON
3
.
2
are controlled by Control Input #2; Sync Input is ignored.
5
(switch 3 ON), NAC Outputs 1 & 2 are controlled by Control Input #1 and
2
are controlled by Control Input #2; Sync Input is monitored
2
which will generate a Temporal code signal without sync; Sync Input is
2
which will generate a Temporal code signal without sync; Sync Input
3
.
3
.
Table 3.1 DIP Switch Settings
OFF
HPF24S configured for Master Synchronization - default
No Delay in AC Fail Reporting
Aux. Trouble Relay responds only to AC Fail/brownout.
Internal trouble contact will not respond to AC loss.
2
are controlled by Control Input #1;
2
are controlled by Control Input #1;
3
.
2
are controlled by Control Input #1;
2
are controlled by Control Input #1;
4
Enable Charger - default
Output Circuit #4 = NAC - default
Programming Options
1
.
21