Advertisement

Applications

5.6 Master HPF24S Power Supply Connected to FACP

In this application, a master HPF24S power supply, set for synchronization, is connected to an
FACP NAC with no synchronized output.
Standby Polarity Shown
Notes: The following notes apply to this Figure 5.6.
1.
Refer to NFPA 72, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
36
HPF24S
Horn/Strobes
(no synchronization)
Figure 5.6 Supervised FACP to Master Connections
Master HPF24S Power Supply Connected to FACP
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
general alarm
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)