Start-Up Procedure - Honeywell HPF24S8 Installation Manual

Field charger/power supply
Hide thumbs Also See for HPF24S8:
Table of Contents

Advertisement

System Overview
– 4.0 amps for HPF24S6
– 6.0 amps for HPF24S8
Maximum total short term current (one hour maximum):
– 6.0 amps for HPF24S6
– 8.0 amps for HPF24S8
Integral supervised battery charger for lead acid batteries only
Capable of charging 7.0 AH to 18.0 AH (Amp Hour) batteries
Fully supervised power supply, battery and NACs
Selectable Strobe Synchronization for NACs (System Sensor, Gentex, and Wheelock)
Coded signal synchronization
Fixed terminal blocks for field wiring capable of accepting 12 - 22 AWG wire
Selectable Ground Fault detection by jumper JP1
Power supply trouble Form-C relay contacts (fail-safe)
Optional delay of AC loss reporting for 2 hours
Special Application Auxiliary Power Output for SLC modules (500 mA maximum) with
optional reset for 4-wire smoke detectors
Mounting location for optional addressable control module

1.3 Start-up Procedure

1.
Configure the power supply jumpers as described in "Jumpers" on page 11.
2.
Install the power supply as described in Section 2, "Installation", on page 15.
3.
Program the power supply as described in Section 3, "Programming Options", on page 20.
4.
Wire the power supply circuits, referring to the options described in Section 4, "Trouble
Supervision", on page 25 and the application examples in Section 5, "Applications", on page
28.
5.
Connect primary power source wiring while observing the following:
– Make certain that the AC mains circuit breaker is off before making any wiring connections
between the mains and the power supply.
– Make certain primary power source is 120 VAC, 60 Hz, 3.2 amps.
– Run a pair of wires (with ground conductor) from the protected premises main breaker box
to TB1 of the power supply main circuit board.
– Use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V insulation.
6.
Apply power to the power supply using the following procedure:
– Apply AC power by turning on the AC mains circuit breaker connected to the power supply.
– Connect a properly charged battery to connector JP4 on the power supply main circuit
board.
10
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
Start-up Procedure

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf24s6Hpf24s6eHpf24s8eHpf24s6cHpf24s8c

Table of Contents