Current Requirements (Standby And Alarm); Current Drawn From Host Panel; Current Drawn From Battery - Honeywell Gamewell FCI GFPS-9 Installation Manual

Supplementary notification appliance circuit module
Table of Contents

Advertisement

9001-0024
the switching power supply circuit.
Note: The use of this knock out will reduce the number and/or size
of batteries this cabinet can contain. Evaluation of space is
important before using.
Ground fault and wire to wire short impedance to any terminal is 0 Ω.
4.3

Current Requirements (Standby and Alarm)

4.3.1

Current Drawn From Host Panel

Table 4-1 shows the GFPS-9 current draw requirements from the main control panel when the panel's
notification appliance circuit is in alarm. The current draw from the main panel when it is supervising the
GFPS-9 is the same current draw that would be present when the main panel supervises an ordinary notification
appliance circuit.
Table 4-1: Alarm Current Drawn From Main Control Panel
Alarm Current (for typical voltages) drawn
from main panel's notification appliance
circuits.
4.3.2

Current Drawn from Battery

Batteries used with the GFPS-9 must not exceed 35AH. (33AH max. for FM (Factory Mutual) Installations).
Batteries larger than 7 AH will not fit into the GFPS-9 cabinet and must be housed in the BC-1 Battery Cabinet.
Figure 4-1 Sample Wire Routing
Panel Voltage
12 VDC
24 VDC
4-6
Current
6.5 mA
One input circuit:
15 mA
Both input circuits:
30 mA