Output Circuit Control DIP Switch Settings

Display Trouble History Mode
To see past troubles on the system, place position 9 to OFF and position 10 to ON. Refer to Section 4 for descriptions of troubles. Trouble
history will be erased upon exiting the Display Trouble History operating mode.
The behavior of the Display Trouble History Mode with regard to the Sync Input Configuration and Trouble reporting will depend on which
was the last active (minimum 5 minutes) operating mode, Default or Retrofit, before entering Display Trouble History Mode.
DIP switch positions 9 and 10 are used to select the type of operating mode as listed below:
3.2 Output Circuit Control DIP Switch Settings
Each output circuit has its own programming DIP switch. DIP switches S2-S8 are labeled on the PCB to indicate which output circuit it is
controlling. Output circuits are labeled at the top of the PCB, TB8-TB14.The following table applies to DIP Switches S2-S8.
Important! If an output circuit is overloaded, the output will shut off and generate a trouble signal. If this happens, the SK-PS will need to be
reset manually. Either reset circuit configurations by toggling switch S1 position 10 to the OFF position for a minimum of five seconds or
turn off primary and secondary power and reapply to the SK-PS.
DIP Switch Position
3
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
SK-PS Series Instruction Manual — P/N LS10227-002SK-E:C 2/2/2022
Position 9
OFF
ON
OFF
ON
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
4
5
6
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
7
OFF
ON
8
OFF
ON
Table 3.9 S2-S8 Output Circuit DIP Switch Settings
Position 10
OFF
Retrofit Mode
OFF
Change output circuit configurations
ON
Display Trouble History
ON
Default Mode
Table 3.8 Operating Mode
Output Control Setting/Operation
NAC output will activate when Command Input #1 is activated.
Do not use this setting when Input#1 is set to Sync Configuration.
NAC output will activate when Command Input #2 is activated.
(Exception: this Input controls Horn silencing during Selective Silence operation.)
NAC output will activate when Command Input #3 is activated, if available. (If
accidentally programmed on a SK-PS6, the system will default to Input #2.)
NAC output will activate when ANY Command Input is activated.
If Input #1 is set to Sync Configuration (Global DIP switch 3 = OFF), this setting applies
to Input#2 and Input#3 only.
Output Control Setting/Operation
Unused/Unsupervised. Outputs will not activate. Factory default setting.
Reserved- Outputs will not activate
Non-resettable auxiliary power
Resettable aux power
Door holder auxiliary power
Slave Configuration (NAC follower)
Master Configuration - ANSI Temporal (Temporal 3)
Master Configuration - CO Temporal (Temporal 4)
Master Configuration - Amseco/Potter
Master Configuration - Gentex
Master Configuration - System Sensor
Master Configuration - Wheelock
Master Configuration, Selective Silence - Amseco/Potter
Master Configuration, Selective Silence - Gentex
Master Configuration, Selective Silence - System Sensor
Master Configuration, Selective Silence - Wheelock
Output Control Setting/Operation (Only applies when ZNAC-PS is installed)
Class B
Class A
Output Control Setting/Operation (Unused)
Unused/Unassigned
Unused/Unassigned
Operating Mode
Programming Options
27