GFPS-9 Supplementary Notification Appliance Circuit Installation Manual
3.
Connect the red wire from the Battery + terminal to the positive (+) side of battery #1.
4.8

DIP Switch Settings

A 7-position DIP switch on the GFPS-9 board allows you to select the following:
How long the GFPS-9 will wait before indicating a loss of AC.
Which input (Input 1 or Input 2) will control the NACs.
Which NACs to wire as Class A and Class B.
Auxiliary power state.
Which NACs to operate as steady, ANSI temporal, or sync. outputs
Refer to Figure 4-2 for the location of the DIP switch on the GFPS-9 board.
4.8.1

Selecting the Standard Input/Output Configurations

Figure 4-7 and Figure 4-8 show the position of each switch for the non-synchronized input and output
configurations. The position of Switches 4 and 5 does not affect the relationship of inputs to outputs.
Note:
The GFPS-9 checks switches 1, 2, 3, and 6 only when powering up the GFPS-9. If you change these switch settings,
Figure 4-6 Battery Connection