Table of Contents

Advertisement

Programming Options

3.1 DIP Switch Settings

The following table lists the HPF24S programmable features and the switch settings required to
select a particular feature. A detailed description of each feature is presented in the following
pages.
SW1 DIP Switch
1
This switch works in conjunction with switch 2 to determine the Strobe Synchronization Type
2
1 OFF, 2 OFF = no sync (steady +24V) - default
1 OFF, 2 ON = System Sensor
1 ON, 2 OFF = Gentex
1 ON, 2 ON = Wheelock
3
FCPS configured for Slave Synchronization
4
Delay AC Fail Reporting for 2 Hours - default
Aux. Trouble Relay responds to all troubles
Internal Trouble contact responds to AC loss
5
This switch works in conjunction with switch 6 to determine Input to Output functions
6
5 OFF, 6 OFF = General Alarm - default
• FCPS configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Sync Input is ignored.
• FCPS configured as Slave (switch 3 ON), NAC Outputs 1 through 4
Sync Input is monitored
• Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 & 10. Control Input
#2 determines if reset will occur (must go from On to Off for a minimum 6 second reset to occur).
• Output #4 function follows DIP switch 8 setting.
5 OFF, 6 ON = Split Alarm
• FCPS configured as Master (switch 3 OFF), NAC Outputs 1 & 2 are controlled by Control Input #1 and
Outputs 3 & 4
• FCPS configured as Slave
Outputs 3 & 4
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
5 ON, 6 OFF = Split Temporal
• FCPS configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2 and Control Input
#2 controls Outputs 3 & 4
• FCPS configured as Slave (switch 3 ON), Control Input #1 controls NAC Outputs 1 & 2 and Control Input #2
controls Outputs 3 & 4
for Outputs 1 & 2
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
5 ON, 6 ON = Selective Silence
• FCPS configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Sync Input is ignored.
• Control Input #2 determines when Selective Silence for all outputs will occur
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
• Output #4 function follows DIP switch 8 setting.
7
Disable Charger
8
Output Circuit #4 = Door Holder
1 Strobe Synchronization only works with non-coded NACs.
2 If Door Closer function is selected (switch 8 ON), Output 4 does not function as an NAC, therefore sync input is
ignored for it.
3 If no synchronization is selected by switches 1 & 2, the Sync Input is ignored.
4 When using Split Alarm with power supply configured for Slave Mode, System Sensor cannot be used (use
System Sensor with Master Mode only).
5 Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning
off the strobe.
20
ON
3
.
2
are controlled by Control Input #2; Sync Input is ignored.
4
(switch 3 ON), NAC Outputs 1 & 2 are controlled by Control Input #1 and
2
are controlled by Control Input #2; Sync Input is monitored
2
which will generate a Temporal code signal without sync; Sync Input is ignored.
2
which will generate a Temporal code signal without sync; Sync Input is monitored
3
.
Table 3.1 DIP Switch Settings
FCPS configured for Master Synchronization - default
No Delay in AC Fail Reporting
Aux. Trouble Relay responds only to AC Fail/Brownout
Internal Trouble contact does not respond to AC loss
2
are controlled by Control Input #1;
2
are controlled by Control Input #1;
3
2
are controlled by Control Input #1;
Enable Charger - default
Output Circuit #4 = NAC - default
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011