Technibel AUS-07H53F010P Series Service Manual

Split air conditioner wall mounted type

Advertisement

Quick Links

Split air conditioner
Wall mounted Type
AUS-07H53F010Px
AUS-07C53F010Px
AUS-09C53F010Px
AUS-09H53F010Px
Service manual
https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html
,
AUS-12H53F110Px
AUS-12C53F150Px
AUS-12H53F150Px
(X=1,2,3,
,
)
,
.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AUS-07H53F010P Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Technibel AUS-07H53F010P Series

  • Page 1 Split air conditioner Wall mounted Type Service manual AUS-07H53F010Px AUS-12H53F110Px AUS-07C53F010Px AUS-12C53F150Px AUS-09C53F010Px AUS-12H53F150Px (X=1,2,3, AUS-09H53F010Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 2: Table Of Contents

    CONTENTS Contents Safety precautions Installation Block diagram Trouble shooting Fault diagnosis by symptom Control specification To disassemble mechanical parts Exploded views and parts list Wiring diagrams https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 3: Safety Precautions

    SAFETY PRECAUTIONS The following safety precautions must be taken when using your air conditioner. 1. Warning: Prior to repair, disconnect the power cord. 2. Use proper parts: use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.) 3.
  • Page 4: Installation Diagram Of Indoor Unit And Outdoor Unit

    INSTALLATION Installation diagram of indoor unit and outdoor unit Confirm the installation position by the mark of the indoor mounting plate. Note Different models have different mounting plates, the installing charts of this book are presented just for the purpose of illustration, please take the real objects as reference.
  • Page 5 INSTALLATION Securing the mounting plate and drill on the wall Note:Different models have different mounting plates, the installing charts of this book are presented just for the purpose of illustration, please take the real objects as reference. Secure the mounting plate The mounting plate should be attached to the structural part of wall (post etc).
  • Page 6: Installation Of The Drain Hose

    INSTALLATION Wiring Diagram Open the front grille; Remove the screw from electrical box cover, pull the Screw electrical box cover away from the unit and set aside. Remove the screw from fastener, pull the fastener away from the unit and set aside. Connecting cable Connect the cable.
  • Page 7: Arrangement Of The Drain Hose

    INSTALLATION Arrangement of the drain hose To drain the condensate water easily, the drain hose should be declined downwards. The following 5 arrangement methods are incorrect. Decline Decline Dip hose Standing water 50mm or less downward downward into water above floor Water Water Water...
  • Page 8 INSTALLATION Installation diagram of indoor unit and outdoor unit Wiring Outdoor unit terminal Outdoor unit terminal Connecting Connecting cable cable Wiring For Above 6000W Model (Above 21000BTU/h Model) 1 Remove the self-tapping screws (2 pcs) The cable wire can be led from the back hole on the maintenance board and take out the of the piping hole or ejecting hole.
  • Page 9 INSTALLATION Notice: If the signal wire has to be bought separately, choose electric wire above 0.75mm. If the interconnection cord for power supply has to be replaced, please see the following table for reference. MODEL SPECS (Interconnection cord) 1.0mm 2700W(10000BTU/h) 3000W(11000BTU/h) -4000W(15000BTU/h) 1.5mm 4500W(18000BTU/h) -8000W(28000BTU/h)
  • Page 10: Air Exhausting

    INSTALLATION Installation of the drain joint(only for heat pump type) Insert the outdoor double-channel drain joint in one of the bottom holes of the suitable size then connect drain hose Bottom and joint together. Double-channel drain joint Drain hose Joint of the connecting pipe Put some seal oil to cover the joint and the flare.
  • Page 11: Adding Refrigerant

    INSTALLATION Adding refrigerant If the connecting pipe is longer than 7 metres, add refrigerant as needed. (Cool only type) added amount A=(Lm-7m) 15g/m ; (Heat pump type)added amount A= (Lm-7m) 50g/m. ( A: amount of added refrigerant, L: the length of connecting pipe) The length of connecting pipe (m) (Cool only type)added amount (g) (Heat pump type)added amount (g)
  • Page 12: Block Diagram

    INSTALLATION Operation test Before test operation, wiring safety inspection must be carried out carefully again. 1. Emergency switch operation: Every press of emergency switch, the air conditioner runs as in the following order: Cool only type: Cool Shut off Heat pump type: Cool Heat Shut off 2.
  • Page 13: Trouble Shooting

    TROUBLE SHOOTING Items to be checked first 1. Is the voltage of the power correct? The input voltage shall be rating voltage 10%. The air conditioner may not operate properly if the voltage is out of this range. 2. Is the link cable connecting the indoor unit and the outdoor unit linked properly? Please refer to the “wiring diagram”...
  • Page 14: Fault Diagnosis By Symptom

    FAULT DIAGNOSIS BY SYMPTOM Fan motor or its capacitor faults. Fan motor Loose connection or badly contact. error No cooling Control circuit error. Voltage may appear a little lower or higher. compressor Loose or wrong connection. does not operate Compressor faults or jumps for overloading. No cooling effect at all Control circuit error.
  • Page 15 FAULT DIAGNOSIS BY SYMPTOM Fan motor or its capacitor faults. Fan motor Loose connection or badly contact. error No heating Control circuit error. Voltage may appear a little lower or higher. compressor Loose or wrong connection. does not operate Compressor faults or jumps for overloading. No heating effect at all Control circuit error.
  • Page 16 FAULT DIAGNOSIS BY SYMPTOM Fixing bolts somewhere may loose or rub, some Collision sound spare parts may not match very well. of the machine Noisy Refrigerant circulation or pressure change of Flowing sound refrigerant while switch on/off. of the liquid Noise from indoor unit Vane imbalance or distortion, rupture;...
  • Page 17 FAULT DIAGNOSIS BY SYMPTOM Switching on the air conditioner Junction wire looses and collides with the outer The current leakage switch cover. jumps to turn off Degraded capability of wire insulation. Check the resistance Insulation capability of of every component some components has by multimeter lowered.
  • Page 18: Control Specification

    CONTROL SPECIFICATION ABBREVIATION ST: Setting Temperature PT: Indoor coil Pipe Temperature RT: Room Temperature OT: Outdoor coil pipe temperature OFAN: Outdoor fan IFAN: Indoor fan COMP: Compressor OPERATION OF MAIN BOARD COOL MODE The ST at cool mode is adjustable within16 -31 . When RT ST, both the compressor and the outdoor fan start;...
  • Page 19: Heat Mode

    CONTROL SPECIFICATION HEAT MODE If the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will take approximately 3 minutes for the compressor to start. The ST at heat mode is adjustable within16 -31 . When RT ST, the compressor stops;...
  • Page 20: Dry Mode

    CONTROL SPECIFICATION DRY MODE In this mode, the air conditioner automatically sets the room temperature and this temperature is incontrollable by remote controller. The initial ST =RT-2 . Control during dry mode: a. When RT<15 , dry mode is not available; when RT 15 , the compressor intermittently runs under the influence of TS and RT.
  • Page 21: Fan Mode

    CONTROL SPECIFICATION FAN MODE In this mode, the outdoor unit does not operate. The indoor fan alone operates. Press UP & DOWN SWING button or LEFT & RIGHT SWING button to change air flow direction. Press FAN SPEED button to change the fan speed of indoor unit. LIGHT-WAVE MODE (only applied to light-wave series) Every press of LIGHT-WAVE button, the air conditioner will cycle in the order of enter/quit light-wave mode.
  • Page 22 CONTROL SPECIFICATION SLEEP mode Normal sleep When the air conditioner is in cooling and dry mode, the indoor fan runs at low speed After one hour of operation the set temperature will increase by 1 .One hour later, the set temperature will increase by once more.
  • Page 23 CONTROL SPECIFICATION Sleep mode 3 When the air conditioner is in cooling and dry mode and 23 st 16 , during the 3 hours after sleep mode 3 start up, the set temperature will increase by 1 every hour .The unit will continue operating at 3 above the set temperature.
  • Page 24: To Disassemble Mechanical Parts

    TO DISASSEMBLE MECHANICAL PARTS Stop operation of the air conditioner and remove the power cord before repairing the unit. The following pictures taking P1 as an example are presented just for the purpose of illustration. Indoor unit Parts Procedure Remark Front grille 1.Stop the air conditioner operation and block the...
  • Page 25 TO DISASSEMBLE MECHANICAL PARTS Parts Procedure Remark 1.Loosen the earth screw in Electrical evaporator. parts 2.Loosen the s tepping motor line, and p ull softly the indoor pipe temperature sensor out from the pipe casing. 3.Push the hook outside to take the electrical box out easily.
  • Page 26 TO DISASSEMBLE MECHANICAL PARTS Parts Procedure Remark 2.Separete the ass’y tray drain from the body. 1.Push the left hook and separate the left part out of evaporator. 2.Push the right hook and separate the right part out of evaporator. Evaporator 3.Separate the evaporator from the indoor unit.
  • Page 27: Outdoor Unit

    TO DISASSEMBLE MECHANICAL PARTS Outdoor unit Parts Procedure Remark Cabinet 1.Turn off the unit and remove the power cable. 2.Remove the upper cabinet, the front cabinet and back cabinet. Fan motor & 1.Remove the nut flange. propeller fan (Turn to the right to remove as it a left turned screw ) 2.separate the propeller fan from fan motor.
  • Page 28: Exploded Views And Parts List

    Exploded Views and Parts List Indoor unit https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 29 Exploded Views and Parts List Indoor unit English Part Name Quantity No. English Part Name Quantity Electrical control box with air Temperature sensor sensitive display (optional) sensitive display Temperature sensor panel(optional) sensitive display Terminal block piece(optional) Display electrical control box Spring piece Grounded terminal Electrical control box...
  • Page 30 Exploded Views and Parts List AUS-07C53F010Px Outdoor unit AUS-09C53F010Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 31 Exploded Views and Parts List AUS-07C53F010Px Outdoor unit AUS-09C53F010Px No. English Part Name Quantity No. English Part Name Quantity Air outlet grille Front panel Left handle Top cover Outdoor unit fan Outdoor fan motor Outdoor fan motor supporter Condenser Partition Electrical install board supporter 11 Left back side plate 12 Back cover...
  • Page 32 AUS-07H53F Exploded Views and Parts List AUS-09H53F010Px Outdoor unit AUS-07H53F010Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 33 Exploded Views and Parts List AUS-09H53F010Px Outdoor unit AUS-07H53F010Px Number Name Quantity Number Name Quantity Air outlet grille Right handle Front panel Outdoor pipe sensor Left handle Top cover Outdoor unit fan Outdoor fan motor Outdoor fan motor supporter Condenser Partition Four way valve Electrical install board supporter...
  • Page 34 Exploded Views and Parts List Outdoor unit AUS-12H53F110Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 35 Exploded Views and Parts List Outdoor unit AUS-12H53F110Px No. English Part Name Quantity No. English Part Name Quantity Air outlet grille 28 Fan motor capacitor Front panel Outdoor unit fan Outdoor fan motor Outdoor fan motor supporter Condenser Left handle Top cover Left back side plate 10 Right back side plate...
  • Page 36 Exploded Views and Parts List Outdoor unit AUS-12C53F150Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 37 Exploded Views and Parts List Outdoor unit AUS-12C53F150Px No. English Part Name Quantity No. English Part Name Quantity Air outlet grille Front panel Outdoor unit fan Partition Valve board Compressor screw Power supply cord fixs Power supply cord clip Capacitor for compressor 10 Electrical install board 11 Right side board 12 Top cover...
  • Page 38 Exploded Views and Parts List AUS-12H53F150Px Outdoor unit https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 39 Exploded Views and Parts List Outdoor unit AUS-12H53F150Px No. English Part Name Quantity No. English Part Name Quantity Air outlet grille Front panel Outdoor unit fan Partition Valve board Compressor screw Power supply cord fixs Power supply cord clip Capacitor for compressor 10 Electrical install board 11 Right side board 12 Top cover...
  • Page 40: Wiring Diagrams

    Wiring Diagrams AUS-07H53F010Px AUS-12H53F150Px Indoor unit AUS-12H53F110Px AUS-09H53F010Px IFAN AUS-07H53F010Px Outdoor unit AUS-12H53F110Px AUS-09H53F010Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 41 Wiring Diagrams AUS-07C53F010Px AUS-12C53F150Px Indoor unit AUS-09C53F010Px IFAN AUS-09C53F010Px AUS-07C53F010Px Outdoor unit AUS-12C53F150Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...
  • Page 42 Wiring Diagrams Outdoor unit AUS-12H53F150Px https://splitsystema48.ru/instrukcii-po-ekspluatacii-kondicionerov.html...