Hybrid smoke prevention system for evacuation routes (99 pages)
Summary of Contents for mercor FID S c/P Series
Page 1
Ul. Grzegorza z Sanoka 2 80 – 408 Gdańsk tel. (0-58) 341 42 45 tel./fax (0-58) 341 39 85 OPERATION AND MAINTENANCE MANUAL Fire damper type mcr FID S/… c/P Version FID C 25.06.03.25 FIRE VENTILATION SYSTEMS DEPARTMENT...
The operation and maintenance manual does not concern the dampers manufactured before the date of its publication. MERCOR – 2/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
Page 3
A thermal release for a damper equipped with KW1 or RST mechanism: 72 ºC 95 ºC Thermal fuse for temperature Tmax 40 ºC Tmax 60 ºC Temperature fuse inside the duct MERCOR – 3/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
The sealing at the partition circumference is effected by a rubber gasket installed on the partition. The enclosure is ended from both ends with flange connections. MERCOR – 4/23 The company reserves the right to modify and change the document.
Page 5
BFL 24-T (-ST) EXBF 230 BFN 230-T EXBF 24 BFN 24-T (-ST) BF 24-TN-TL MF 230-T1 MF 24-T1 MLF 230-T1 MLF 24-T1 MERCOR – 5/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
FID S/… c/P fire damper with RST Gear RST/KW1 130 30 * embedding border mcr FID S/… c/P fire damper with RST/KW1 MERCOR – 6/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
(B+90) x (H+90) mm. • for dampers installed in a dry system, filling the gap between the wall and the damper: (B+100) x (H+100) mm MERCOR – 7/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
Fulfilling this comment is a condition of keeping the product warranty. partition spacer body Securing the gap size between the damper body and the partition. MERCOR – 8/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
Page 9
NOTE It is crucial to observe the device embedding border, so that the release and control mechanism is outside the separation wall and allows easy access. MERCOR – 9/23 The company reserves the right to modify and change the document.
Page 10
The manufacturer allows the use of other materials with parameters not worse than the recommended solution and has the appropriate approval documents confirming the appropriate class of fire resistance. MERCOR – 10/23 The company reserves the right to modify and change the document.
Page 11
The manufacturer allows the use of other materials with parameters not worse than the recommended solution and has the appropriate approval documents confirming the appropriate class of fire resistance. MERCOR – 11/23 The company reserves the right to modify and change the document.
Page 12
(e.g. plasterboard) with a thickness of at least 10 mm for flexible walls and 15 mm for rigid walls. Installation of the mcr FID S/... c/P fire damper in the wall close to the ceiling MERCOR – 12/23 The company reserves the right to modify and change the document.
Page 13
Polylac Elastic thickness 1mm, according to the picture above. The manufacturer allows the use of other materials with parameters not worse than the recommended solution and has the appropriate approval documents confirming the appropriate class of fire resistance. MERCOR – 13/23 The company reserves the right to modify and change the document.
- Belimo BFN series Open isolation partition – actuator indication: 90 - Belimo BF series Closed isolation partition – actuator indication: 0 - Mercor MF series - Mercor MLF series - Belimo serii BE Open isolation partition – actuator indication: 0 - Belimo serii BLE Closed isolation partition –...
Page 15
55 dB (A) - spring ~ 62 dB (A) ~ 62 dB (A) ~ 67 dB (A) ~ 67 dB (A) MERCOR – 15/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
Page 16
Connection diagram for the BF24-Tand BF230-T actuators Connection diagram for the BFL24-T, BFL230-T, BFN24-T, BFN230-T, BF24-TN and BF230-TN actuators Connection diagram for the BE24, BLE24, BE230 and BLE230 actuators MERCOR – 16/23 The company reserves the right to modify and change the document.
Page 17
For proper operation of a device equipped with electrical actuators, it is recommended that the rated voltage housed tolerance of 24V±10% or 230V±10%. Power supply devices other than listed above may cause malfunction and will not be covered by the warranty conditions. MERCOR – 17/23 The company reserves the right to modify and change the document.
Page 18
NO/NC (changeover switch) WK1d or WK2d limit switch 5A, 230V AC Limit switches actuation 3°, 87°, ±2° tolerance Limit switches working -25 ...+85°C temperature MERCOR – 18/23 The company reserves the right to modify and change the document. Version FID C 25.06.03.25...
Page 19
We put the fuse cells on hooks attached to the damper body and to the partition. With the nut we pull and lock the hook by tightening so that the flap baffle is completely open • MERCOR – 19/23 The company reserves the right to modify and change the document.
Storage should take place in rooms where: • there is no access to dust, gases, caustic vapors and other aggressive chemical vapors that can destroy insulating elements and structural elements; MERCOR – 20/23 The company reserves the right to modify and change the document.
In the matters related with technical inspections, maintenance and the device service, contact the representatives of the Service Department of MERCOR serwis@mercor.com.pl, tel. 058/ 341 42 45 internal 170 or fax 058/ 341 39 85 from 8 AM to 8 PM (Mon - Fri).
Page 22
The buyer/warranty rights holder modifies the product design without prior authorisation from MERCOR • Periodic technical inspection and/or maintenance is not carried out per schedule and/or is carried out by unauthorised personnel or service providers not authorised to do so by MERCOR and/or the equipment has not been properly operated. •...
Page 23
FID S/… c/P single-plane fire dampers 1396 MERCOR S.A. and 380-470 1396-CPR-0114 PN-EN 15650:2010 (EN 15650:2010) Fire damper mcr FID S/S c/P Nominal activation conditions / sensitivity: Positive result sensor activation temperature Positive result - reliability sensor Response time:...
Need help?
Do you have a question about the FID S c/P Series and is the answer not in the manual?
Questions and answers