Page 1
ul. Grzegorza z Sanoka 2 80-408 Gdańsk Phone: (0-58) 341 42 45 tel./fax (0-58) 341 39 85 OPERATION AND MAINTENANCE MANUAL (OMM) mcr FID PRO type fire damper Rev. FID PRO 20.08.19.12 FIRE VENTILATION SYSTEMS DEPARTMENT...
7. TRANSPORT AND STORAGE CONDITIONS ...................... 16 8. MAINTENANCE AND SERVICE (REPAIRS) ......................17 9. WARRANTY TERMS AND CONDITIONS ......................17 Markings used in the OMM Option available Option unavailable 2/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
The fire damper’s cut-off partition is made of non-flammable board. The partition is lined on both sides with sheet metal reinforcement. On the 3/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 4
It is recommended that the fire damper were opened and closed when the ventilation system is turned off. 4/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 5
Main dimensions female connection type (muff) Gear BF 24TL-ST EXBF 225 190 55 100 male connection type (nipple) * embedding border version with circumferential seal type F 5/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 6
(nipple) embed symmetrically with respect to axis mcr FID PRO fire damper with RST female connection type (muff) Gear RST/KW1 * embedding border 6/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Trigger control gear Connection method Damper type 1 – connection method: N or [no symbol] – male connection (nipple) M – female connection (muff) K – flange 7/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
125 mm walls made of boards with the minimum thickness of 125 mm structural floors with the minimum thickness of 150 mm 8/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Preparation of the mounting hole for dampers installed using mortar Preparation of the mounting hole for dampers installed using mineral wool 6.3. BUILDING IN (EMBEDDING) THE FIRE DAMPER NOTE 9/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 10
Expansion of the seals makes it impossible to close the fire damper. After the installation has been completed, clean thoroughly the fire damper and ensure that no debris has been left inside, as it could affect its correct operation. 10/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 11
The minimum depth of filling with mortar for the length of the body of the device. Installation of the mcr FID PRO fire damper with a spring mechanism in masonry walls, brickwork walls or blockwork walls using mineral wool 11/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 12
The minimum depth of filling with mortar for the length of the body of the device. Installation of the mcr FID PRO fire damper with an electric mechanism in masonry walls, brickwork walls or blockwork walls using mineral wool 12/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 13
2. E.g. cement mortar X – structural floor thickness Installation of the mcr FID PRO fire damper with an electric mechanism in structural floors using mortar 13/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 14
7. Mineral wool with a density min. 150 kg/m3 X – wall thickness Installation of the mcr FID PRO fire damper with an electric mechanism in walls made of boards 14/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Location of the damper isolation partition - Belimo BFL series Open isolation partition – actuator indication: 90 - Belimo BFN series Closed isolation partition – actuator indication: 0 15/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 16
FID PRO single-plane fire dampers - Belimo BF series - Mercor MLF series - Belimo serii BE - Belimo serii BLE Open isolation partition – actuator indication: 0 - Belimo serii BEE Closed isolation partition – actuator indication: 90...
Page 17
55 dB (A) max 55 dB (A) - spring ~ 62 dB (A) ~ 67 dB (A) ~ 67 dB (A) ~ 62 dB (A) 17/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 18
Connection diagram for the BF24-Tand BF230-T actuators Connection diagram for the BFL24-T, BFL230-T, BFN24-T, BFN230-T, BF24-TN and BF230-TN actuators Connection diagram for the BE24, BLE24, BE230 and BLE230 actuators 18/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 19
2 x SPDT 6A (3) max. 250 V AC 2 x SPDT 6A (3) max. 250 V AC – activation point 5°, 80° 5°, 80° Torque: – motor 18 Nm 18 Nm 19/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 20
Wire no. 3–4, NO type (normally open) Wire no. 6–7, NO type (normally open) Wire no. 4–5, NC type (normally closed) Wire no. 7–8, NC type (normally closed) 20/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
Page 21
Technical data (limit switches) WK1 and WK2 limit switches 1 x NO/1 x NC SPDT (changeover switch) 5A, 230V AC Limit switches working temperature -25 ...+85°C Housing plastic 21/24 „MERCOR” SA – the Company reserves the right to make modifications and changes.
“MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase, unless the sales contract states otherwise. Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty eligible defect 22/24 „MERCOR”...
Page 23
Item 10. “MERCOR” SA has the right to extend the time of repair if the defect removal is complicated or requires purchase of custom components or spare parts.
Page 24
13. Any circumstances listed in Item 10 will relieve “MERCOR” SA from the obligation of surety. The relevant provisions of the Polish Civil Code shall apply to all matters not regulated in these Warranty Terms & Conditions.
Need help?
Do you have a question about the mcr FID PRO Series and is the answer not in the manual?
Questions and answers