mercor mcr WIP EI60S Operation And Maintenance Manual

Fire damper

Advertisement

Quick Links

OPERATION AND
MAINTENANCE MANUAL
MAINTENANCE MANUAL
mcr WIP type fire
Rev. WIP 15.06.15.3
FIRE VENTILATION SYSTEMS DEPARTMENT
FIRE VENTILATION SYSTEMS DEPARTMENT
FIRE VENTILATION SYSTEMS DEPARTMENT
(OMM)
damper
Ul. Grzegorza z Sanoka 2,
Ul. Grzegorza z Sanoka 2,
80-408 Gda
408 Gdańsk
Phone (0-
-58) 341 42 45

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the mcr WIP EI60S and is the answer not in the manual?

Questions and answers

Summary of Contents for mercor mcr WIP EI60S

  • Page 1 Ul. Grzegorza z Sanoka 2, Ul. Grzegorza z Sanoka 2, 80-408 Gda 408 Gdańsk Phone (0- -58) 341 42 45 OPERATION AND MAINTENANCE MANUAL MAINTENANCE MANUAL (OMM) mcr WIP type fire damper Rev. WIP 15.06.15.3 FIRE VENTILATION SYSTEMS DEPARTMENT FIRE VENTILATION SYSTEMS DEPARTMENT FIRE VENTILATION SYSTEMS DEPARTMENT...
  • Page 2: Table Of Contents

    7. TRANSPORT AND STORAGE CONDITIONS ...................... 15 8. MAINTENANCE AND SERVICE (REPAIRS) ......................16 9. WARRANTY TERMS AND CONDITIONS ......................16 Markings used in the OMM Option available Option unavailable 2/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 3: Introduction

    The maximum surface area of the mcr WIP type fire damper is 1 m . The minimum surface area of a fire damper is 0.019 m 3/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 4: Design And Operating Principle Of The Fire Damper

    Never try to open or close a fire damper’s partition by pulling it directly. Such attempts may cause damage to the self-locking powertrain of a fire damper and this is not covered by warranty. 4/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 5: Manufacturer's Designation Of The Fire Damper

    5.MANUFACTURER’S DESIGNATION OF THE FIRE DAMPER mcr WIP / S 400 (width) x 400 (height) Release and control mechanism Net dimensions of the fire damper’s opening Fire damper type/application 5/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 6: Installation Of The Fire Damper

    The minimum size of an installation opening necessary for correct installation of the mcr WIP type fire damper is: Bo = (A + Bz + 80) [mm] Ho = (H + 180) [mm] Mixture EXBF C1 [mm] A [mm] 6/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 7 2.ST4.2x16 sheet metal screw 4.E.g. cement mortar 6.Heat-resistant seal X – Wall thickness Example illustrating how to install the mcr WIP type fire damper in masonry and concrete walls 7/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 8 3. Mcr WIP type fire damper, W x 6. Heat-resistant seal Example illustrating how to install the mcr WIP type fire damper in walls made of boards 8/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 9 2. Protective grid 3. Mcr WIP type fire damper, W x H Example illustrating how to install a protective grid for the mcr WIP type fire damper 9/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 10 Thickness: 1.25 mm Also, the condition of grid thickness depending on thickness of the wall (in which the fire damper has been installed), has to be satisfied. 10/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 11: Electrical Connections

    Partition closed – actuator indication 0˚ - Belimo BE series Partition open – actuator indication 0˚ - Belimo BLE series Partition closed – actuator indication 90˚ 11/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 12 3°, 87° 3°, 87° 3°, 87° Torque: - motor 40 Nm 40 Nm 15 Nm 15 Nm - locking 50 Nm 50 Nm 20 Nm 20 Nm 12/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 13 Notice: 24 V connection through a safety transformer. Several actuators may be connected in parallel. Power consumption should be monitored. Wiring diagram for BFL24-T, BFL230-T, BFN24-T and BFN230-T actuators 13/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 14 - motor 150 s 150 s - return spring ≈ 20 s ≈ 20 s Ambient temperature −20 ...+50°C −20 ...+50°C Wiring diagram for EXBF actuators 14/17 MERCOR SA – the Company reserves the right to make modifications and changes.
  • Page 15 Normally open state is indicated WK1 and WK2 limit switches wiring diagram WK1 and WK2 limit switches wiring diagram 15/17 MERCOR SA – the Company reserves the right to make modifications and changes. the Company reserves the right to make modifications and changes.
  • Page 16: Transport And Storage Conditions

    21 days from the receipt of a written complaint and a proof of purchase or agreement, subject to item 6. MERCOR SA reserves the right to extend the repair time in the case of complex repairs or those necessitating a purchase of non-standard components or spare parts.
  • Page 17 11. In the cases referred to in item 10, the liability of MERCOR SA under statutory warranty is also excluded. 12. The condition for removal of defects is the complaining party’s making available full access to the products in...