Page 1
Introduction Application The OS2 AC Controller is a 230 V ac control The OS2 230 V 6A ac Controller forms the basis of the SE Controls mains unit designed for use with 4 wire 230 V ac voltage solutions. actuators in a natural ventilation system.
Contents General Information Fault Finding 4.1. Push Buttons 1.1. General Safety Information 4.2. Indicators 1.2. Health and Safety Volt Free Status Connectors 1.3. Environment Fuses 1.4. User Responsibilities 1.5. Maintenance 1.6. Installation and Connection 1.7. Fault Finding 1.8. Contact Information 1.9.
Important Notices • The equipment has no • Failure to install the SE Controls accepts mains on/off switch and is device in accordance no liability for failure to comply with these intended for permanent with the manufacturer’s connection only. instructions will invalidate statements or the any warranties.
If recycling facilities are not locally available, is assembled carefully and the settings are carried out according to these instructions and contact SE Controls who can arrange for recycling to the operating instructions of the drives. and disposal of old electronic products.
Tel: 01543 443060 E-mail: info@secontrols.com Website: www.secontrols.com 1.9. Certification SE Controls hereby certify that the parts and services detailed hereon have been manufactured, inspected, tested and supplied in accordance with the conditions and requirements of the procedures as documented in the Company Quality Assurance System to ensure conformance with SE Controls’...
Specification 2.1. Device Overview Part Number FCS00210001 OS2 230 V 6A ac Controller 1 Zone Dimensions 220 x 209 x 124 mm (W x D x H) Power Class 1 Mass Approx. kg (approx) Supply 230 V ac 50/60Hz from a 6A unswitched spur Current Rating Real Time Clock Battery Life 10 Years IP Rating IP20...
The installer must not adjust or remove original manufacturers cabling or use terminal outputs or inputs for purposes other than their design purposes without the written authorization from SE Controls. Please keep these operating instructions for future +44 (0)1543 443060 reference and maintenance.
Connection to the actuators is made using 3 core + earth cable of suitable cross-section to carry the maximum actuator current. In operation, the actuator power is timed off automatically after a period defined for the mode of operation. For Caretaker, Rain and Thermostat demands this period is 180 seconds (Factory adjustable). For day to day and 0-10 V demands the default period is 18 seconds (Factory adjustable). The default actuator output mode is for motor open/motor close actuators. Other devices (such as magnetic catches) can be selected at the factory by SE Controls. Please keep these operating instructions for future +44 (0)1543 443060 reference and maintenance. Subject to technical sales@secontrols.com modifications. Diagram is not binding.
3.4. Control Connections Each controller can operate either as a stand alone unit or as part of a BMS managed control system. To allow for this level of control complexity, 7+1 control inputs are provided in the basic controller. The following list identifies the 7 controls in their priority order; Caretaker Demand Slave Demand &...
3.8. Rain Sensor Connecting RNS to 0 V will close all attached actuators. By default, the thermostat, Day to Day and 0-10V inputs are all ignored under this condition. The lockout of the Day to Day input and 0-10 V inputs can be modified at the factory by SE Controls. By default, breaking the connection between RNS and 0 V will not alter the position of the actuators (factory adjustable). In operation, the actuator power is automatically timed off after a period of 180 seconds (factory adjustable). This is a sufficient length of time to ensure most actuators achieve their fully closed position as required. To prevent ‘machine gun’ operation of the actuators, rain sensor movements are also subject to the 180 second (factory adjustable) lockout period, during which period other rain sensor input changes are ignored.
3 position switch having 2 normally open contacts is used. In operation, power is applied to the actuator only during the period when one of the contacts is closed. This mode of operation is factory adjustable by SE Controls. In the open direction, the actuator power is automatically timed off when a total period of 18 seconds (factory adjustable) is exceeded.
The exception to this is if the input voltage is set to 0 V. In this case, the controller will apply power in the close direction to the actuator but will time off after a period of 180 seconds (factory adjustable) to guarantee the fully closed position is reached. By default, the 0-10 V input is assumed to be an automatic control but can be adjusted at the factory by SE Controls to be a manual control. 3.12.
3.13. Network Connection Connections NA, NB and SCR are used for forming network connections between controllers. The use of networking requires the installation of an OSLink card and reference to their individual user manuals which are outside the scope of this document. Please keep these operating instructions for future +44 (0)1543 443060 reference and maintenance. Subject to technical sales@secontrols.com modifications.
Fault Finding 4.1. Indicators Colour Detail LD1 WINK Factory use only. LD2 HLTY Green Healthy Lamp - Lit when the controller has not identified any internal faults. LD3 POW Green Lit when Mains supply is connected. LD4 WDG Yellow Watchdog - Flashes to indicate software running in controller OK. LD5 OPN Lit when output energized to open LD6 CLS Green Lit when output energized to close...
Page 15
Lancaster House Wellington Crescent sales@secontrols.com Fradley Park, Lichfield www.secontrols.com Staffordshire WS13 8RZ Name & registered office: Loanguard Limited, Lancaster House, Wellington Crescent, Fradley Park, Lichfield, Staffordshire WS13 8RZ Company No.01468061 Vat No.377 5600 30 - SE Controls is a Registered Trademark...