Advertisement
PAX Lite Current and Volt Meters are premium quality instruments designed for tough industrial applications. With multi-range capability, built-in provision for scaling, and DIP switch selectable decimal points, these meters offer the ultimate in application flexibility. Four models cover your voltage and current indicator needs. The meter can provide direct readout from pressure, speed or flow transducers, or any other variable that can be translated to voltage or current. The built-in scaling allows the display to be scaled to the desired engineering unit.
The 3 ‰ -digit bi-polar display (minus sign displayed when current or voltage is negative) features a 0.56" high, 7-segment LEDs for easy reading. The meter is also available with custom units label capability. Using the PAX label kit (PAXLBK30), the selected label is installed behind the panel, keeping it safe from washdown or other environmental conditions. A DIP switch is used to control the backlight for the units label.
The meters have a NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE requirements, allowing the meter to provide a tough yet reliable application solution.
Risk of Danger. Read complete instructions prior to installation and operation of the unit.
Risk of electric shock.
In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
Meter Part Numbers
Accessories Part Numbers
TYPE | MODEL NO. | DESCRIPTION | PART NUMBERS |
Accessories | PAXLBK | Units Label Kit Accessory | PAXLBK30 |
APSCM | 10 Amp DC Current Shunt | APSCM010 | |
100 Amp DC Current Shunt | APSCM100 |
AC Voltmeters | AC Current Meters | DC Voltmeters | DC Current Meters |
0-1.999 V/1 mV | 0-199.9 µA/0.1 µA | ±1.999 V/1 mV | ±199.9 µA/0.1 µA |
0-19.99 V/10 mV | 0-1.999 mA/1 µA | ±19.99 V/10 mV | ±1.999 mA/1 µA |
0-199.9 V/100 mV | 0-19.99 mA/10 µA | ±199.9 V/100 mV | ±19.99 mA/10 µA |
0-300 V/1 V | 0-199.9 mA/100 µA | ±300 V/1 V | ±199.9 mA/100 µA |
0-1.999 A/1 mA | ±1.999 A/1 mA | ||
0-199.9 mV/100 µV | ±199.9 mV/100 µV |
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2 No. 61010-1
Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #UL/8843A/UL CB Scheme Test Report #04ME11209-20041018 Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1. IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY:
Immunity to Industrial Locations:
Electrostatic discharge | EN 61000-4-2 | Criterion A 4 kV contact discharge 8 kV air discharge |
Electromagnetic RF fields | EN 61000-4-3 | Criterion B 10 V/m |
Fast transients (burst) | EN 61000-4-4 | Criterion B 2 kV power 2 kV signal |
Surge | EN 61000-4-5 | Criterion A 1 kV L-L, 2 kV L&N-E power |
RF conducted interference | EN 61000-4-6 | Criterion A 3 V/rms |
Voltage dip/interruptions | EN 61000-4-11 | Criterion A 0.5 cycle; 40% variation |
Emissions: Emissions | EN 55011 | Class B |
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, Control and Laboratory use.
Notes:
UNITS LABEL KIT (PAXLBK)
Each meter has a units indicator with backlighting that can be customized using the Units Label Kit. The backlight is controlled by a DIP switch.
EXTERNAL CURRENT SHUNTS (APSCM)
To measure DC current signals greater than 2 ADC, a shunt must be used. The APSCM010 current shunt converts a maximum 10 ADC signal into 100.0 mV. The APSCM100 current shunt converts a maximum 100 ADC signal into 100.0 mV. The continuous current through the shunt is limited to 115% of the rating.
Installation
The PAX meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel (Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
The meter has an input jumper and switches, which must be checked and/or changed prior to applying power. To access the input jumper and switches, remove the meter base from the case by firmly squeezing and pulling back on the side rear finger tabs. This should lower the latch below the case slot (which is located just in front of the finger tabs). It is recommended to release the latch on one side, then start the other side latch.
Power Selection Switch
Insure the AC power selection switch is set for the proper voltage before powering the meter. The meter is shipped from the factory in the 230 VAC position.
Input Range Jumper
A jumper is used for selection of the voltage or current input range. Select the proper input range that will be high enough to avoid input signal overload. It is important that only one jumper position is used at a time. Avoid placing a jumper across two different input ranges.
Set-Up DIP Switches
ADIP switch is located inside the meter. It is used for the selection of decimal points, backlight annunciator, and scaling. Selecting the ON position enables the function.
SWITCH | FUNCTION |
1 | Decimal Point 1 (000.0) |
2 | Decimal Point 2 (00.00) |
3 | Decimal Point 3 (0.000) |
4 | Backlight Annunciator for Units Label |
5 | Enables the Scaling Pot |
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter s voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the meter (AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the meter case against those shown in wiring drawings for proper wire position. Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded wires should be tinned with solder). Insert the lead under the correct screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.)
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, its source or the method of coupling into the unit may be different for various installations. Listed below are some EMC guidelines for successful installation in an industrial environment.
POWER WIRING
AC Power
Terminal 1: VAC
Terminal 2: VAC
INPUT SIGNAL WIRING
Before connecting signal wires, the Input Range Jumper should be verified for proper position.
PAXLV
Voltage Signal (self powered)
Terminal 4: + Volts DC/AC
Terminal 3: - Volts DC/AC
PAXLI
Current Signal (self powered)
Terminal 4: + Amps DC/AC
Terminal 3: - Amps DC/AC
PAXLV
DIRECT VOLTMETER READOUT
When the application requires direct voltmeter readout, the Scale Switch should remain in the OFF position. The Input Range Jumper is set to the voltage range being applied. It is possible to select a range higher than being applied to get lower resolution. The Decimal Point switches are set to resolution of the selected Input Range Jumper.
SCALING VOLTMETER READOUT
In many industrial applications, a voltmeter is required to display a reading in terms of PSI, RPM, or some other unit of measure. The signal voltage being measured can be generated by a transducer that senses the variations and delivers a linear output voltage. To provide the desired readout at the specified voltage, the voltmeter must be scaled.
Place the Scale Switch in the ON position. This enables the Scale Potentiometer which is accessible from the back of the meter. (Enabling the Scale Potentiometer does NOT affect the calibration of the meter.) Place the Decimal Point Switches to the proper location. To properly set the Input Range Jumper, the Division Factor must be determined by first using the below formula. After the Division Factor is calculated, use the Division Factor Range Selection Chart to choose the proper Input Range Jumper setting. Apply the meter power and the voltage signal. Adjust the Scale Potentiometer to the desired value.
This scaling only effects the span. There is no offset scaling. This means that only zero voltage can display a value of zero.
DIVISION FACTOR FORMULA:
WHERE:
VT = Maximum Transducer Output
D.D.P = Display Decimal Point
D.F. = Division Factor
D.R. = Desired Reading
D.D.P.
0.000 = 1
00.00 = 10
000.0 = 100
0000 = 1000
The Display Decimal Point (D.D.P.) is determined by the desired decimal point placement in the readout.
After the Division Factor for the application has been calculated, the proper voltage range jumper can be selected. Use the Division Factor Range Selection Chart to choose the proper jumper setting.
DIVISION FACTOR RANGE SELECTION CHART
D.F. | Use Input Position |
0.1 to 1.2 | Pos 1: 0-1.999 VDC |
1.2 to 10.5 | Pos 2: 0-19.99 |
10.5 to 100.5 | Pos 3: 0-199.9 |
100.5 to 1300 | Pos 4: 0-300 |
Note: Only one voltage jumper should be selected. Install the jumper before the voltage signal is applied.
BLOCK DIAGRAM PAXLV
EXAMPLE: A relative humidity transducer delivers a 7.0 VDC voltage at a relative humidity of 75%.
This Division Factor is between 10.5 and 100.5, therefore jumper position 3 (199.9 V) is selected. The Scaling Potentiometer is then adjusted for the desired readout at a known relative humidity.
DIRECT CURRENT METER READOUT
When the application requires direct current meter readout, the Scale Switch should remain in the OFF position. The Input Range Jumper is set to the current range being applied. It is possible to select a range higher than being applied to get lower resolution. The Decimal Point switches are set to resolution of the selected Input Range Jumper.
SCALING CURRENT METER READOUT
In many industrial applications, a current meter is required to display a reading in terms of PSI, RPM, or some other unit of measure. The signal voltage being measured can be generated by a transducer that senses the variations and delivers a linear output voltage. To provide the desired readout at the specified current, the current meter must be scaled.
Place the Scale Switch in the ON position. This enables the Scale Potentiometer which is accessible from the back of the meter. (Enabling the Scale Potentiometer does NOT affect the calibration of the meter.) Place the Decimal Point Switches to the proper location. The Input Range Jumper is set to the current range being applied. Apply the meter power and the current signal. Adjust the Scale Potentiometer to the desired value. Scaling to obtain a numerical readout higher than the normal value of the current can also be accomplished, in most cases, by selecting a lower current range. However, the maximum current for the range must not be exceeded. (See Specifications for maximum input currents.)
This scaling only effects the span. There is no offset scaling. This means that only zero amps can display a value of zero.
BLOCK DIAGRAM PAXLI
EXAMPLE: The Pax Current Meter has been connected to measure a circuit current to 120.0 mA maximum. However, in this application, the display is to indicate percent of load current with 120.0 mA equivalent to 100.0 percent. The scale potentiometer is adjusted to reduce the normal 120.0 mA signal input display reading of 120.0 to indicate the desired reading of 100.0 on the display. Scaling to obtain a numerical readout higher than the normal value of the current can also be accomplished in most cases by selecting a lower current range. However, the maximum current for the range must not be exceeded. (See Specifications for maximum input currents.)
PROBLEM | REMEDIES |
NO DISPLAY | CHECK: Power switch and line voltage |
INCORRECT DISPLAY | CHECK: Input jumper position CHECK: Scaling adjustment pot DIP switch position ADJUST: Scaling pot VERIFY: Input Signal |
OVER-RANGE INDICATION | CHECK: Input jumper position VERIFY: Input signal |
The meter has been fully calibrated at the factory. Scaling to convert the input signal to a desired display value is performed by enabling the scale pot DIP switch. If the meter appears to be indicating incorrectly or inaccurately, refer to Troubleshooting before attempting to calibrate the meter.
When recalibration is required (generally every 2 years), it should only be performed by qualified technicians using appropriate equipment.
Input Calibration
Calibration of this meter requires a signal source with an accuracy of 0.01% or better and an external meter with an accuracy of 0.005% or better.
Before starting, verify that the Input Range Jumper is set for the range to be calibrated. Also verify that the precision signal source is connected and ready.
Allow a 30 minute warm-up period before calibrating the meter. Then perform the following procedure:
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
DEFINITION OF TERMS
INSTALLATION CATEGORY (overvoltage category) I, (CAT I):
Signal level, special equipment or parts of equipment, telecommunication, electronic, etc. with smaller transient overvoltages than Installation Category (overvoltage category) II. (See IEC 664 & IEC 61010)
INSTALLATION CATEGORY (overvoltage category) II, (CAT II):
Local level, appliances, portable equipment, etc. with smaller transient overvoltages than Installation Category (overvoltage category) III. (See IEC 664 & IEC 61010)
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download red lion PAX Series, PAX LITE PAXLI / PAXLV / PAXLVA00 / PAXLID00 Manual
Advertisement
Need help?
Do you have a question about the PAX Series and is the answer not in the manual?
Questions and answers