Group 3: Output Function Parameters
3-00
Analog Output Signal (AFM)
Settings
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
The voltage output type for this analog signal is PWM. It needs to read value by the movable
coil meter and is not suitable for A/D signal conversion.
3-01
Analog Output Gain
Settings
The parameter sets the voltage range of the analog output signal at terminals AFM, that
corresponds with either the output frequency or the output current of the VFD.
The analog output voltage is directly proportional to the output frequency of the AC drive. With
the factory setting of 100%, the Maximum Output Frequency (Pr.1-00) of the AC drive
corresponds to +10VDC analog voltage output. (The actual voltage is about +10VDC, and
can be adjusted by Pr.3-01).
The analog output voltage is directly proportional to the output current of the AC drive. With
the factory setting of 100%, the 2.5 times rated current of the AC drive corresponds to
+10VDC analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by
Pr. 3-01)
NOTE
Voltmeter specification: The sourcing capability of the output is limited to 0.21mA. Sourcing voltage:
If the meter reads full scale at a voltage less than 10 volts, then Pr.3-01 should be set by
the following formula: Pr.3-01 = ((meter full scale voltage)/10) ×100%
For example: When using the meter with full scale of 5 volts, adjust Pr.3-01 to 50%.
Revision August 2006, SE08, SW V2.61
d0
Analog Frequency Meter (0 to Maximum Output Frequency)
d1
Analog Current Meter (0 to 250% of rated AC motor drive current)
d1 to d200%
AFM
GND
+
-
Analog Frequency Meter
10V. Output resistance: 47kΩ.
Chapter 5 Parameters|VFD-S Series
AFM
GND
+
-
Analog Current Meter
Factory Setting: d0
Unit: 1
Factory Setting: d100
5-31