Over-voltage
detection
level Pr.6-01
6-02
Over-Current Stall Prevention Level
Settings
A setting of 100% is equal to the Rated Output Current of the drive.
During acceleration and steady-state operation, the AC drive output current may increase
abruptly to exceed the value specified by Pr.6-02 due to rapid acceleration or excessive load
on the motor. When this function is enabled, the AC drive will decrease. The AC drive will only
resume acceleration when the current drops below the level specified by Pr. 6-02.
Over-current
detection
level
Pr.6-02
Revision August 2006, SE08, SW V2.61
DC bus voltage
Output
Freq.
Over-voltage Stall Prevention
d20 to d150%
Output current
Output
frequency
Over-current Stall Prevention Level
Chapter 5 Parameters|VFD-S Series
Band=20V
time
time
Factory Setting: d130
ON
Band=5%
OFF
time
time
Unit: 1
5-53