Delta Electronics AC Motor Drive VFD007S23A User Manual page 127

Delta electronics ac motor drive user manual
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-S Series
Content
3.6 Exception response:
The AC motor drive is expected to return a normal response after receiving command
messages from the master device. The following depicts the conditions when no
normal response is replied to the master device.
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout
condition.
The AC motor drive receives the messages without a communication error, but cannot handle
them. An exception response will be returned to the master device and an error
message "CExx" will be displayed on the keypad of AC motor drive. The xx of "CExx"
is a decimal code equal to the exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and
an exception code which explains the condition that caused the exception is
returned.
5-72
Address
35: Reserved
36: PID error (Pld)
37: Reserved
38: Phase loss (PHL)
2101H
Status of AC Drive
Bit 0-1
Bit 2
Bit 3-4
Bit 5-7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12-15
2102H
Frequency command F (XXX.XX)
2103H
Output Frequency H (XXX.XX)
2104H
Output Current A (XXX.XX)
2105H
DC-BUS Voltage U (XXX.XX)
2106H
Output Voltage E (XXX.XX)
2107H
Step number of Multi-Step Speed Operation
2108H
Step number of PLC operation
2109H
Time of PLC Operation
210AH
Counter Value
Functions
00: RUN LED light off, STOP LED light up
01: RUN LED blink, STOP LED light up
10: RUN LED light up, STOP LED blink
11: RUN LED light up, STOP LED light off
01: Jog active
00: REV LED light off, FWD LED light up
01: REV LED blink, FWD LED light up
10: REV LED light up, FWD LED blink
11: REV LED light up, FRD LED light off
Not used
1: Main freq. Controlled by communication
1: Main freq. Controlled by external terminal
1: Operation command controlled by communication
1: Parameters have been locked
Not Used
Revision August 2006, SE08, SW V2.61